{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C106MA100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C106MA100","canonicalUrl":"https://aoctrl.com/schneider/C106MA100","factsUrl":"https://aoctrl.com/api/mcp/products/C106MA100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100-250, trip unit MA100, magnetic, 100 A, 4P 3D, motor short-circuit protection, EN/IEC 60947-2.","salesMarkdown":"The C106MA100 is a magnetic-only trip unit from the ComPacT NSX100...250 range, designed for motor short-circuit protection (protection type I) in AC networks. It carries a 100 A rating at 65 °C, so it's sized for a motor full-load current up to that thermal limit — the magnetic element handles fault clearing, not overload. The instantaneous pick-up is adjustable from 6 to 14 times In (600 A to 1400 A), which lets you set the magnetic threshold above the motor's starting inrush without nuisance tripping. This is a 4-pole unit with 3 protected poles (3D) — the neutral pole is unprotected, so it's intended for three-phase motor circuits where the neutral carries no load. Fixed-mount trip unit for ComPacT NSX100, NSX160, or NSX250 molded-case circuit breakers. The neutral position is left, and the unit snaps into the breaker's trip-unit cradle — no wiring required beyond the breaker's own terminals. IP40 protection (IEC 60529) covers the trip unit itself; the overall breaker enclosure may carry a higher rating. Ambient operating range is -25 to 70 °C, storage from -50 to 85 °C — fine for most indoor panel installations, though you'll want to check the breaker's own derating curve if the panel ambient exceeds 40 °C.","metaTitle":"C106MA100 ComPacT NSX MA100 trip unit, 100 A, motor protecti","metaDescription":"C106MA100 magnetic trip unit for ComPacT NSX100-250, 100 A at 65 °C, motor short-circuit protection, EN/IEC 60947-2, active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C106MA100","Standards":"EN/IEC 60947-2","description":"Trip unit MA100, ComPacT NSX100/160/250, 4 poles 3D (neutral not protected), magnetic, motor protection, 100A rating","Network type":"AC","Trip unit name":"MA","Protection type":"I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60947-1","Range of product":"ComPacT NSX100...250","Trip unit rating":"100 A at 65 °C","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Motor","Trip unit technology":"Magnetic","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Trip unit","Neutral protection settings":"No protection (3D)","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","Trip unit protection functions":"I","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Ii] instantaneous protection pick-up adjustment range":"6...14 x In"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$110.08 – $138.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e1ccea7f67834f63ba752bdf2a8aaaf3.pdf","sourceUrl":"https://www.se.com/au/en/product/C106MA100/trip-unit-ma100-compact-nsx100-160-250-4-poles-3d-neutral-not-protected-magnetic-motor-protection-100a-rating/"},"ai":{"faq":[{"question":"What is C106MA100 used for?","answer":"It is a magnetic trip unit for motor short-circuit protection in ComPacT NSX100-250 circuit breakers. It provides adjustable instantaneous magnetic protection (6-14 x In) but no overload protection — an external overload relay is required."},{"question":"What standards does C106MA100 comply with?","answer":"It complies with EN/IEC 60947-2 (low-voltage switchgear and controlgear — circuit-breakers). Pollution degree 3 per IEC 60947-1, and IP40 per IEC 60529."},{"question":"Where can I buy C106MA100?","answer":"The C106MA100 is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C106MA100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C106MA100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}