{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C106TM016C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C106TM016C","canonicalUrl":"https://aoctrl.com/schneider/C106TM016C","factsUrl":"https://aoctrl.com/api/mcp/products/C106TM016C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100 series, TM-D thermal-magnetic trip unit, C106TM016C, 16 A at 50 °C, 4 poles 3D, EN/IEC 60947-2.","salesMarkdown":"## What this trip unit does in the panel It provides LI protection — thermal overload (L) via a bimetal element and fixed magnetic short-circuit (I) pickup at 190 A. The 16 A rating at 50 °C means it's sized for a 16 A continuous load in a 50 °C ambient; above that temperature the thermal curve derates per IEC 60947-2. The fixed instantaneous trip at 190 A gives a 11.9x In ratio — that's a high magnetic pickup, so it avoids nuisance trips on moderate motor inrush but still clears a hard fault fast. The 690 V AC / 750 V DC rated operational voltage (Ue) covers most industrial distribution voltages — 400 V, 480 V, 600 V AC, and 250 V DC strings. IP40 front-face protection handles finger contact but not washdown — it's a panel-mount device, not a standalone enclosure. The adjustable long-time pickup (Ir) from 0.7 to 1.0 x In lets you fine-tune the overload threshold between 11.2 A and 16 A without swapping the trip unit. Fixed long-time delay (tr) at 120–400 s at 1.5 x Ir gives a standard inverse-time curve for cable and busbar protection — not for motor overload, which needs a separate overload relay.","metaTitle":"C106TM016C ComPacT NSX100 TM-D Trip Unit, 16 A, 4P 3D","metaDescription":"C106TM016C thermal-magnetic trip unit, 16 A at 50 °C, 4 poles 3D, EN/IEC 60947-2. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C106TM016C","Standards":"EN/IEC 60947-2","description":"Trip unit TM16D, ComPacT NSX100, thermal magnetic, rating 16A, 50 degrees C, 4 poles 3D","Network type":"AC DC","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60947-1","Range of product":"ComPacT NSX100...250","Trip unit rating":"16 A at 50 °C","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Trip unit technology":"Thermal-magnetic","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Trip unit","Neutral protection settings":"No protection (3D)","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 750 V DC","Electrical shock protection class":"Class II","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","Long-time protection delay adjustment type tr":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"190 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/df8e749f619a2f7787366b8951d16ede.pdf","sourceUrl":"https://www.se.com/sa/en/product/C106TM016C/trip-unit-tm16d-compact-nsx100-thermal-magnetic-rating-16a-50-degrees-c-4-poles-3d/"},"ai":{"faq":[{"question":"What is C106TM016C's listed range and standards?","answer":"It belongs to the ComPacT NSX100...250 range and complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear."},{"question":"Where can I buy C106TM016C?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C106TM016C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C106TM016C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}