{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C106TM080C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C106TM080C","canonicalUrl":"https://aoctrl.com/schneider/C106TM080C","factsUrl":"https://aoctrl.com/api/mcp/products/C106TM080C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100...250, TM-D trip unit, 80 A at 50 °C, 4 poles 3D, thermal-magnetic, EN/IEC 60947-2.","salesMarkdown":"## TM-D trip unit for ComPacT NSX It is rated 80 A at 50 °C, with 4 poles configured as 3D (three protected poles, no neutral protection). ## Rating and protection settings The long-time pickup (Ir) is adjustable from 0.7 to 1.0 x In, so you can dial the 80 A rating down to 56 A for cable protection or derating scenarios. The long-time delay (Tr) is fixed, with a characteristic of 120–400 s at 1.5 x Ir and 15 s at 6 x Ir — a standard thermal curve for distribution loads. Instantaneous pickup (Ii) is fixed at 640 A (8 x In), which gives good selectivity with downstream 16–32 A breakers on most panelboard feeds. ## Voltage and environment Rated operational voltage is 690 V AC 50/60 Hz and 750 V DC, so it covers 480Y/277 V and 600 V delta panels, plus DC bus applications up to 750 V. IP40 front face keeps tools and fingers out.","metaTitle":"Schneider C106TM080C ComPacT NSX TM-D Trip Unit, 80 A, 4P","metaDescription":"Schneider Electric C106TM080C TM-D trip unit for ComPacT NSX100-250, 80 A at 50 °C, 4 poles 3D, EN/IEC 60947-2. Active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C106TM080C","Standards":"EN/IEC 60947-2","description":"Trip unit TM80D, ComPacT NSX100/160/250, thermal magnetic, rating 80A, 50 degrees C, 4 poles 3D","Network type":"AC DC","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60947-1","Range of product":"ComPacT NSX100...250","Trip unit rating":"80 A at 50 °C","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Trip unit technology":"Thermal-magnetic","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Trip unit","Neutral protection settings":"No protection (3D)","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 750 V DC","Electrical shock protection class":"Class II","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","Long-time protection delay adjustment type tr":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"640 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/186378b38e0d38cbc3b7d6a5d9bb295e.pdf","sourceUrl":"https://www.se.com/nl/en/product/C106TM080C/trip-unit-tm80d-compact-nsx100-160-250-thermal-magnetic-rating-80a-50-degrees-c-4-poles-3d/"},"ai":{"faq":[{"question":"What is C106TM080C's listed range and standards?","answer":"It belongs to the ComPacT NSX100...250 range and complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear. The trip unit is a TM-D thermal-magnetic type for distribution applications."},{"question":"What are the key ratings for C106TM080C?","answer":"The trip unit is rated 80 A at 50 °C with adjustable long-time pickup (Ir) from 0.7 to 1.0 x In and fixed instantaneous pickup (Ii) at 640 A. Rated operational voltage is 690 V AC / 750 V DC. It has 4 poles configured as 3D (three protected poles, no neutral protection)."},{"question":"Where can I buy C106TM080C and how is it quoted?","answer":"The C106TM080C is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and delivery requirements."},{"question":"What compliance documentation is available for C106TM080C?","answer":"The trip unit carries EN/IEC 60947-2 certification and is rated pollution degree 3 per IEC 60947-1. It is Class II for electrical shock protection. Standard Schneider documentation includes the declaration of conformity and IEC test certificates for the ComPacT NSX family."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C106TM080C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C106TM080C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}