{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10B32D100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10B32D100","canonicalUrl":"https://aoctrl.com/schneider/C10B32D100","factsUrl":"https://aoctrl.com/api/mcp/products/C10B32D100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, C10B32D100, 3P 100A circuit breaker with MicroLogic 2.2 electronic trip unit, 25 kA Icu at 415 V AC, IP40.","salesMarkdown":"The C10B32D100 is a Schneider Electric ComPacT NSX100B molded-case circuit breaker, 3-pole, rated 100 A at 40 °C with a MicroLogic 2.2 electronic trip unit. The MicroLogic 2.2 provides LSoI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). Breaking capacity steps down by voltage: 40 kA at 240 V, 25 kA at 415 V, 20 kA at 440 V, 15 kA at 500 V. ## Panel fit and environment Overvoltage category III suits fixed-installation distribution boards.","metaTitle":"Schneider Electric C10B32D100 ComPacT NSX100B, 100A, 25kA 41","metaDescription":"Schneider Electric C10B32D100 ComPacT NSX circuit breaker, 100A MicroLogic 2.2 trip unit, 25kA at 415V AC. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$252.91 – $523.15","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/46789bba2eb884bfd8260800f2a63c1d.pdf","sourceUrl":"https://www.se.com/th/en/product/C10B32D100/circuit-breaker-compact-nsx100b-25ka-415vac-3-poles-micrologic-2-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10B32D100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10B32D100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10B32D100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}