{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10B34V040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10B34V040","canonicalUrl":"https://aoctrl.com/schneider/C10B34V040","factsUrl":"https://aoctrl.com/api/mcp/products/C10B34V040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100B, earth leakage circuit breaker, 3P, 40 A at 40 °C, 40 kA Icu at 240 V AC, MicroLogic 4.2 electronic trip unit.","salesMarkdown":"It's a 3-pole unit rated 40 A at 40 °C, with an integrated MicroLogic 4.2 electronic trip unit that provides overload (L), short-time short-circuit (So), instantaneous (I), and earth-leakage (R) protection. At 415 V AC the breaking capacity is 25 kA Icu, and at 440 V it's 20 kA Icu, all per IEC 60947-2. That standard certifies the breaker for industrial application, not just residential. ## Deployment context Mounts on a backplate in a distribution panel — horizontal or vertical orientation, flat on the back. The toggle control and front connections (both upside and downside) make it straightforward to wire in a panel layout. Mechanical durability is 50,000 cycles; electrical durability ranges from 50,000 cycles at 440 V at half rated current down to 10,000 cycles at 690 V at full rated current — so if you're switching near its limits frequently, factor that in.","metaTitle":"Schneider Electric C10B34V040 ComPacT NSX MCCB, 40 A, 40 kA","metaDescription":"Schneider Electric C10B34V040 ComPacT NSX 3P earth leakage circuit breaker, 40 A at 40 °C, 40 kA Icu at 240 V AC. MicroLogic 4.2 electronic trip unit. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,014.60 – $1,882.44","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/081631e27894db516cd0ff2ebbb584c3.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10B34V040/circuit-breaker-compact-nsx100b-25ka-415vac-3-poles-micrologic-vigi-4-2-trip-unit-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10B34V040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10B34V040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10B34V040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}