{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F1TM020","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F1TM020","canonicalUrl":"https://aoctrl.com/schneider/C10F1TM020","factsUrl":"https://aoctrl.com/api/mcp/products/C10F1TM020","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, 1-pole 20 A thermal-magnetic circuit breaker, 18 kA Icu at 240 V AC, 36 kA Icu at 250 V DC, toggle control, IP40, EN/IEC 60947-2.","salesMarkdown":"The C10F1TM020 is a 1-pole ComPacT NSX100F thermal-magnetic circuit breaker rated 20 A at 40 °C, built to EN/IEC 60947-2 for distribution duty. The TM-D trip unit gives you L (thermal overload) and I (magnetic short-circuit) protection in one compact fixed-mount package — no earth-leakage module on this variant. Fixed backplate mount, 35 mm width per pole, 161 mm tall, 86 mm deep. 20 A continuous at 40 °C ambient. 18 kA breaking capacity at 240 V AC, 36 kA at 250 V DC. 20000 mechanical cycles, 20000 electrical cycles at rated current. Power dissipation 4.01 W per pole. Overvoltage category IV — suitable for main distribution boards. Operating altitude 0–2000 m without derating, up to 5000 m with derating.","metaTitle":"C10F1TM020 ComPacT NSX100F 1P 20A Thermal-Magnetic MCB, 18kA","metaDescription":"C10F1TM020 ComPacT NSX100F 1-pole 20A thermal-magnetic circuit breaker. 18kA Icu at 240V AC, 36kA at 250V DC. EN/IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10F1TM020","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"35 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX100F AC/DC, 18kA/240VAC, 1 pole, TMD trip unit 20A","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"20 A at 40 °C","Breaking capacity":"18 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"20 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"F 18 kA 240 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.01 W","Protected poles description":"1D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"277 V AC 50/60 Hz 250 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"18 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"190 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$74.43","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/14f373a20e5d28e9415ca3e7f1cdf225.pdf","sourceUrl":"https://www.se.com/th/en/product/C10F1TM020/circuit-breaker-compact-nsx100f-ac-dc-18ka-240vac-1-pole-tmd-trip-unit-20a/"},"ai":{"faq":[{"question":"What is C10F1TM020's breaking capacity?","answer":"18 kA Icu at 220/240 V AC 50/60 Hz per IEC 60947-2, and 36 kA Icu at 250 V DC per the same standard."},{"question":"What trip unit does C10F1TM020 use?","answer":"A TM-D thermal-magnetic trip unit, rated 20 A at 40 °C. The L protection handles overloads (thermal), the I protection handles short-circuits (magnetic). No earth-leakage function on this variant."},{"question":"Where can I buy C10F1TM020 and how is it quoted?","answer":"Sourced through independent distribution channels. Quoted to order against an RFQ — availability and current pricing confirmed at quote time. No minimum volume commitment required for a quote."},{"question":"What compliance documentation does Schneider provide for C10F1TM020?","answer":"The breaker is certified to EN/IEC 60947-2, carries IP40 per IEC 60529, IK07 per IEC 62262, and is rated for pollution degree 3 per IEC 60664-1 and overvoltage category IV. Standard manufacturer declarations for CE/UKCA marking apply."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F1TM020","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F1TM020 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}