{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F1TM030","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F1TM030","canonicalUrl":"https://aoctrl.com/schneider/C10F1TM030","factsUrl":"https://aoctrl.com/api/mcp/products/C10F1TM030","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100F, 1-pole thermal-magnetic MCCB, 30 A at 40 °C, 18 kA breaking capacity at 240 V AC.","salesMarkdown":"The Schneider Electric C10F1TM030 is a ComPacT NSX100F circuit breaker, 1-pole, with a TM-D thermal-magnetic trip unit rated 30 A at 40 °C. It breaks 18 kA Icu at 240 V AC (50/60 Hz) per IEC 60947-2, and 36 kA Icu at 250 V DC — that DC rating is unusual for a single-pole frame this size, useful if you are isolating a DC bus in a pitch-control cabinet or brake resistor circuit up-tower. The 36 kA at 250 V DC is a separate rating — do not assume the same performance at 125 V DC or 48 V DC; consult the coordination tables if you are using it on a battery bank. The TM-D trip unit provides thermal overload protection (L) and magnetic short-circuit protection (I). At 30 A and 40 °C ambient, the thermal element tracks RMS current; below 40 °C it trips slightly slower, above 40 °C you must derate per the IEC 60947-2 thermal curve. The magnetic pickup is fixed at roughly 10× In (300 A), so it will not nuisance-trip on motor inrush unless the motor draws over 300 A locked-rotor. Mounts on a backplate — not DIN-rail — so plan for screw-down fixing with the 35 mm pole pitch aligning to busbar or cable lugs. The 161 mm height and 86 mm depth fit a standard enclosure, but the 35 mm width per pole means a 1-pole unit occupies one module slot. Front connections top and bottom simplify busbar runs in a distribution board. The IK07 impact rating means it survives a 2 J hammer blow during panel assembly.","metaTitle":"C10F1TM030 ComPacT NSX100F 30A 1P 18kA MCCB","metaDescription":"C10F1TM030 ComPacT NSX100F MCCB, 30A thermal-magnetic trip, 1-pole, 18kA at 240V AC. Active production. Sourced to order. Inquire for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"35 mm","Height":"161 mm","Voltage":"277 V AC 50/60 Hz 250 V DC","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"750 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$74.43","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f7b58bdf4a15d3f56fb664ce78b2b772.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10F1TM030/circuit-breaker-compact-nsx100f-ac-dc-18ka-240vac-1-pole-tmd-trip-unit-30a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F1TM030/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F1TM030","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F1TM030 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}