{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F1TM040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F1TM040","canonicalUrl":"https://aoctrl.com/schneider/C10F1TM040","factsUrl":"https://aoctrl.com/api/mcp/products/C10F1TM040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100F, thermal-magnetic MCCB, 1-pole, 40 A at 40 °C, 18 kA Icu at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"It protects a single pole (1P, 1D protected) against overload (thermal element L) and short-circuit (magnetic element I). The 18 kA Icu at 220/240 V AC (50/60 Hz) per IEC 60947-2 tells you it can safely interrupt faults up to that level without welding or rupturing — enough for most distribution panels fed from a transformer of moderate size. At 250 V DC it handles 36 kA Icu, so it also works on DC bus or battery circuits where the arc is harder to extinguish. The 35 mm width and 161 mm height let it slot into a standard backplate-mounted panel alongside other ComPacT units. IK07 impact rating means it survives a hard knock from a dropped tool during panel work. If your panel runs hotter, you derate — the TM-D curve shifts. Power dissipation is 5.47 W per pole, so a 1-pole unit dumps about 5.5 W into the enclosure. In a dense panel with multiple breakers, that heat adds up — account for it in the thermal budget. The electrical durability is 20,000 cycles at rated current and 10,000 cycles at twice rated current; mechanical durability is 20,000 cycles. That is typical for a fixed-mount distribution MCCB — not a switching device for frequent operations. Overvoltage category IV means it can be installed at the service entrance or main distribution board where transient overvoltages are highest. Operating altitude is 0–2000 m without derating, 2000–5000 m with derating.","metaTitle":"Schneider C10F1TM040 ComPacT NSX100F MCCB, 40 A, 18 kA","metaDescription":"Schneider C10F1TM040 ComPacT NSX100F MCCB, 40 A thermal-magnetic trip, 18 kA Icu at 240 V AC. EN/IEC 60947-2. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"35 mm","Height":"161 mm","Voltage":"277 V AC 50/60 Hz 250 V DC","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"18 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC conforming to IEC 60947-2","Insulation Voltage Ui":"750 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$74.43","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/757a24c52302236a8890d7d5264b9213.pdf","sourceUrl":"https://www.se.com/vn/en/product/C10F1TM040/circuit-breaker-compact-nsx100f-ac-dc-18ka-240vac-1-pole-tmd-trip-unit-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F1TM040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F1TM040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F1TM040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}