{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F2TM016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F2TM016","canonicalUrl":"https://aoctrl.com/schneider/C10F2TM016","factsUrl":"https://aoctrl.com/api/mcp/products/C10F2TM016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100F, C10F2TM016, 2-pole thermal-magnetic MCCB, 16 A rated, 36 kA breaking capacity at 240 V AC.","salesMarkdown":"## What this MCCB brings to a panel The C10F2TM016 is a Schneider ComPacT NSX100F moulded-case circuit breaker, 2-pole, thermal-magnetic trip unit set at 16 A at 40 °C. It's an active-production part, so no lifecycle surprises when you're filling a BOM or stocking a spare for a distribution board. Mounts on a backplate or flat panel surface, 70 mm wide, 161 mm tall, 86 mm deep. ## Trip curve and protection logic The TM-D trip unit gives you thermal overload protection (L) and magnetic short-circuit protection (I) — no electronic adjustment, no earth-leakage module. For a 16 A circuit feeding lighting, small motor groups, or general distribution, that's a straightforward, field-proven curve that doesn't need a laptop to commission.","metaTitle":"Schneider C10F2TM016 ComPacT NSX100F 16A MCCB, 36kA 240V","metaDescription":"Schneider C10F2TM016 ComPacT NSX100F MCCB, 2-pole, 16A thermal-magnetic trip, 36kA Icu at 240V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"70 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz 500 V DC","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2","Insulation Voltage Ui":"750 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$175.68","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c7bcc573a091975128792f7c8387f996.pdf","sourceUrl":"https://www.se.com/ng/en/product/C10F2TM016/circuit-breaker-compact-nsx100f-ac-dc-18ka-at-415vac-tmd-trip-unit-16a-2-poles-2d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F2TM016/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F2TM016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F2TM016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}