{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F2TM016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F2TM016","canonicalUrl":"https://aoctrl.com/schneider/C10F2TM016","factsUrl":"https://aoctrl.com/api/mcp/products/C10F2TM016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100F, C10F2TM016, 2-pole thermal-magnetic MCCB, 16 A rated, 36 kA breaking capacity at 240 V AC.","salesMarkdown":"## What this MCCB brings to a panel The C10F2TM016 is a Schneider ComPacT NSX100F moulded-case circuit breaker, 2-pole, thermal-magnetic trip unit set at 16 A at 40 °C. It's an active-production part, so no lifecycle surprises when you're filling a BOM or stocking a spare for a distribution board. Mounts on a backplate or flat panel surface, 70 mm wide, 161 mm tall, 86 mm deep. ## Trip curve and protection logic The TM-D trip unit gives you thermal overload protection (L) and magnetic short-circuit protection (I) — no electronic adjustment, no earth-leakage module. For a 16 A circuit feeding lighting, small motor groups, or general distribution, that's a straightforward, field-proven curve that doesn't need a laptop to commission.","metaTitle":"Schneider C10F2TM016 ComPacT NSX100F 16A MCCB, 36kA 240V","metaDescription":"Schneider C10F2TM016 ComPacT NSX100F MCCB, 2-pole, 16A thermal-magnetic trip, 36kA Icu at 240V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10F2TM016","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"70 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX100F AC/DC, 18kA at 415VAC, TMD trip unit 16A, 2 poles 2d","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"16 A at 40 °C","Breaking capacity":"36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"16 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"F 18 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"2.92 W","Protected poles description":"2D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 500 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"190 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$175.68","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c7bcc573a091975128792f7c8387f996.pdf","sourceUrl":"https://www.se.com/ng/en/product/C10F2TM016/circuit-breaker-compact-nsx100f-ac-dc-18ka-at-415vac-tmd-trip-unit-16a-2-poles-2d/"},"ai":{"faq":[{"question":"Where can I buy C10F2TM016 and get a price?","answer":"We source this part through independent distribution; submit an RFQ and we'll confirm availability and current pricing at quote time."},{"question":"What is the breaking capacity of C10F2TM016 at 415 V?","answer":"18 kA Icu at 380/415 V AC, 1-pole conforming to IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F2TM016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F2TM016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}