{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F2TM030","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F2TM030","canonicalUrl":"https://aoctrl.com/schneider/C10F2TM030","factsUrl":"https://aoctrl.com/api/mcp/products/C10F2TM030","rawCanonicalId":null},"summary":{"shortDescription":"Schneider ComPacT NSX C10F2TM030 molded case circuit breaker, 2 poles, 30 A TM-D thermal-magnetic trip unit, 36 kA IC at 690 V AC, fixed mount, toggle control, EN/IEC 60947-2.","salesMarkdown":"## Overview The C10F2TM030 is a Schneider ComPacT NSX molded case circuit breaker with 2 poles, a TM-D thermal-magnetic trip unit rated 30 A at 40 °C, and a breaking capacity of 36 kA at 690 V AC. It is an active, current-production part in the ComPacT NSX new generation line, compliant with EN/IEC 60947-2. ## Alternatives & selection Compared to the C10F3TM025 (3-pole, 25 A, 85 kA IC), the C10F2TM030 offers 2 poles instead of 3, a higher continuous current rating of 30 A versus 25 A, but a lower breaking capacity of 36 kA versus 85 kA. Choose the C10F2TM030 for 2-pole distribution circuits at 30 A where the available fault current stays under 36 kA; the C10F3TM025 suits 3-pole applications with higher fault levels.","metaTitle":"Schneider C10F2TM030 ComPacT NSX MCCB, 2-pole, 30 A, 36 kA","metaDescription":"Schneider ComPacT NSX C10F2TM030 molded case circuit breaker, 2 poles, 30 A TM-D trip, 36 kA IC at 690 V AC, EN/IEC 60947-2. Active product.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"70 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"30 A at 40 °C","Breaking capacity":"36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"30 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"F 18 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.03 W","Protected poles description":"2D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 500 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"300 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$193.12","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b7847e4bfeddb248c70b12e37a6231de.pdf","sourceUrl":"https://www.se.com/ph/en/product/C10F2TM030/circuit-breaker-compact-nsx100f-ac-dc-18ka-at-415vac-tmd-trip-unit-30a-2-poles-2d/"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F2TM030","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F2TM030 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}