{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F2TM050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F2TM050","canonicalUrl":"https://aoctrl.com/schneider/C10F2TM050","factsUrl":"https://aoctrl.com/api/mcp/products/C10F2TM050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, 2-pole, thermal-magnetic, 50 A, 36 kA Icu at 240 V AC, IP40.","salesMarkdown":"It's built for distribution duty in a fixed-mount, 2-pole configuration, and it's certified to EN/IEC 60947-2. At 415 V AC the breaking capacity drops to 18 kA Icu, which is still enough for most commercial distribution boards. The thermal-magnetic trip gives you two protection curves in one package: the thermal element (L) handles overloads — slow, sustained overcurrents from a stalled motor or a loaded feeder — and the magnetic element (I) catches short-circuits instantly. No electronics to fail, no auxiliary power needed to trip. It's the workhorse choice for panels where simplicity and reliability beat adjustability. This breaker mounts on a backplate — fixed, not DIN-rail — so it's for a panel where you bolt the MCCB directly to the mounting plate. The 70 mm width and 161 mm height fit standard enclosure cutouts, and the 86 mm depth leaves room for front-connected cables (both line and load connections are front-facing). The IK07 impact rating means it shrugs off a 2 J hammer blow during installation. The 35 mm connection pitch matches standard busbar spacing. Pollution degree 3 means it's happy in a typical industrial panel with conductive dust or occasional condensation. Rated current: 50 A at 40 °C. Poles: 2. Breaking capacity (Icu): 36 kA at 240 V AC, 18 kA at 415 V AC, 15 kA at 440 V AC, 10 kA at 525 V AC, 5 kA at 690 V AC. DC breaking: 36 kA at 250 V DC (1 pole), 36 kA at 500 V DC (2 poles in series). Electrical endurance: 20,000 cycles at 277 V at In/2, 10,000 cycles at 277 V at In. Mechanical endurance: 20,000 cycles. Power dissipation per pole: 4.11 W. Operating altitude: 0–2000 m without derating, 2000–5000 m with derating. Relative humidity: 0–95 %. Ambient temperature for trip rating: 40 °C.","metaTitle":"Schneider Electric C10F2TM050 ComPacT NSX 50A 2P MCCB, 36 kA","metaDescription":"Schneider Electric C10F2TM050 ComPacT NSX circuit breaker, 50 A, 2-pole, TM-D trip unit, 36 kA Icu at 240 V AC. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10F2TM050","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"70 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX100F AC/DC, 18kA/415VAC, 2 poles, TMD trip unit 50A","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"50 A at 40 °C","Breaking capacity":"36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"50 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"F 18 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.11 W","Protected poles description":"2D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 500 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$175.68","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d880abaa86a5dadd275f026910500df4.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10F2TM050/circuit-breaker-compact-nsx100f-ac-dc-18ka-415vac-2-poles-tmd-trip-unit-50a/"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F2TM050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F2TM050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}