{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F2TM080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F2TM080","canonicalUrl":"https://aoctrl.com/schneider/C10F2TM080","factsUrl":"https://aoctrl.com/api/mcp/products/C10F2TM080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100F, 2-pole circuit breaker, 80 A thermal-magnetic TM-D trip unit, 18 kA Icu at 415 V AC, IP40, toggle control.","salesMarkdown":"The C10F2TM080 is a Schneider Electric ComPacT NSX100F 2-pole fixed-mount circuit breaker with an 80 A thermal-magnetic TM-D trip unit. This is the rating that governs fault interruption on a 400 V line: at 415 V it clears 18 kA symmetrical, enough for most commercial and light industrial panelboards without cascading upstream. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection, with the thermal element calibrated at 40 °C ambient. The C10F2TM080 is listed as current production. IP40 front face and IK07 impact resistance handle normal panel service. ## Mounting & Connections Fixed backplate mount, accepts horizontal or vertical orientation. Front-facing connections top and bottom — 35 mm pitch. The 2-pole form factor (70 mm wide, 161 mm high, 86 mm deep) fits standard panel cutouts.","metaTitle":"Schneider Electric C10F2TM080 ComPacT NSX100F Circuit Breake","metaDescription":"Schneider Electric C10F2TM080 ComPacT NSX100F 2-pole circuit breaker, 80 A thermal-magnetic TM-D trip unit, 18 kA Icu at 415 V AC. Current production status. Sourced to order again","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10F2TM080","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"70 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX100F AC/DC. 18kA at 415VAC. TMD trip unit 80A. 2 poles 2d","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"80 A at 40 °C","Breaking capacity":"36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"80 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"F 18 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"8.77 W","Protected poles description":"2D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 500 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"640 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$175.68","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0934487a1a5c58ab79eb7e2dd859eefd.pdf","sourceUrl":"https://www.se.com/za/en/product/C10F2TM080/circuit-breaker-compact-nsx100f-ac-dc-18ka-at-415vac-tmd-trip-unit-80a-2-poles-2d/"},"ai":{"faq":[{"question":"What is the breaking capacity of C10F2TM080 at 415 V AC?","answer":"18 kA Icu at 380/415 V AC, 1-pole per IEC 60947-2. This is the F breaking capacity code."},{"question":"What trip unit does C10F2TM080 use?","answer":"A TM-D thermal-magnetic trip unit rated 80 A at 40 °C, providing L (thermal overload) and I (magnetic short-circuit) protection."},{"question":"What are the mounting dimensions of C10F2TM080?","answer":"Width 70 mm, height 161 mm, depth 86 mm. Fixed backplate mount with 35 mm connection pitch."},{"question":"Where can I buy C10F2TM080?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F2TM080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F2TM080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}