{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F34V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F34V100","canonicalUrl":"https://aoctrl.com/schneider/C10F34V100","factsUrl":"https://aoctrl.com/api/mcp/products/C10F34V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX100F, 3-pole MCCB with MicroLogic 4.2 electronic trip unit, 100 A at 40 °C, 85 kA Icu at 240 V AC, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C10F34V100 is a ComPacT NSX100F molded-case circuit breaker with a MicroLogic 4.2 electronic trip unit, rated 100 A at 40 °C and delivering 85 kA Icu at 240 V AC. At 415 V the rating drops to 36 kA Icu, still enough for most European industrial feeders. The 4.2 trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection in one package — so this single breaker handles both overcurrent and ground-fault detection, saving a separate RCD. ## Fit and panel integration Mounts on a backplate in horizontal or vertical orientation — no DIN-rail adapter needed. ## Electrical durability and application class Rated for Category A (no intentional short-time delay for selectivity with downstream breakers — it trips instantaneously on short-circuit). Electrical durability is 50,000 cycles at 440 V at half rated current (In/2), and 30,000 cycles at full In. At 690 V the count drops to 20,000 cycles at In/2 and 10,000 at In. Mechanical durability is 50,000 cycles — the toggle mechanism itself outlasts the electrical contacts under heavy fault duty. Overvoltage category IV — suitable for main distribution boards at the service entrance. The integrated earth-leakage protection (R function) means the breaker meets requirements for residual current protection without an external module. Operating altitude is 2000 m without derating; above that, up to 5000 m, derating applies. Relative humidity range is 0 to 95 %, non-condensing.","metaTitle":"Schneider Electric C10F34V100 ComPacT NSX100F MCCB, 100 A, 8","metaDescription":"Schneider Electric C10F34V100 ComPacT NSX100F MCCB. 100 A at 40 °C, 85 kA Icu at 240 V AC. MicroLogic 4.2 electronic trip unit with integrated earth-leakage. EN/IEC 60947-2. Active","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"5.8 W N 5.8 W L1 and L3 4.9 W L2","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"40...100 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,029.46 – $1,928.88","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f6000e518336636f0239cb2591831f24.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10F34V100/circuit-breaker-compact-nsx100f-36ka-415vac-3-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F34V100/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C10F34V100 and how do I get a price?","answer":"The C10F34V100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is C10F34V100's breaking capacity at 415 V?","answer":"At 380/415 V AC 50/60 Hz the C10F34V100 delivers 36 kA Icu per IEC 60947-2. At 440 V it is 35 kA, at 480 V (UL) it is 25 kA, and at 690 V it is 8 kA."},{"question":"What compliance documentation does this brand provide for C10F34V100?","answer":"The C10F34V100 is designed to EN/IEC 60947-2 and carries an overvoltage category IV rating. It is suitable for distribution applications with pollution degree 3 per IEC 60664-1. Specific RoHS/REACH declarations and UL file information are available from the manufacturer's documentation portal."},{"question":"What is the closest alternative to C10F34V100 in the ComPacT NSX family?","answer":"Within the same NSX100F frame, the closest alternative would be a variant with a different trip unit — for example, the MicroLogic 2.3 (thermal-magnetic) instead of the 4.2 (electronic with earth-leakage). The frame, breaking capacity, and dimensions are identical; the difference is in the protection curve and whether integrated earth-leakage is required. For a pin-compatible electronic trip unit with earth-leakage, the C10F34V100 is the standard choice."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F34V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F34V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}