{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F3MA013","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F3MA013","canonicalUrl":"https://aoctrl.com/schneider/C10F3MA013","factsUrl":"https://aoctrl.com/api/mcp/products/C10F3MA013","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NSX series, NSX100F circuit breaker, 3-pole, 12.5 A MA magnetic trip unit, 36 kA breaking capacity at 415 V AC.","salesMarkdown":"## Motor protection breaker, magnetic-only trip The MA trip responds only to short-circuit currents (magnetic protection), leaving overload protection to a separate thermal relay or motor starter — standard practice for motor branch circuits where the starter handles the thermal curve. Rated 12.5 A at 65 °C, it's sized for a motor full-load current in that range, not for general distribution. Breaking capacity is 36 kA Icu at 380/415 V AC, 50/60 Hz per IEC 60947-2. At 220/240 V it delivers 85 kA Icu; at 480 V UL-rated it holds 25 kA. Mounts on a backplate (not DIN rail — the NSX frame uses a screw-fixed backplate mount). Three protected poles (3D), front connection both top and bottom. IP40 front face, IK07 impact resistance.","metaTitle":"Schneider Electric C10F3MA013 ComPacT NSX100F, 12.5 A, 36 kA","metaDescription":"Schneider Electric C10F3MA013 ComPacT NSX circuit breaker, 3-pole, 12.5 A MA magnetic trip, 36 kA at 415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$303.69 – $410.89","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0f7ea1d63501938620a19a941a5f9af9.pdf","sourceUrl":"https://www.se.com/th/en/product/C10F3MA013/circuit-breaker-compact-nsx100f-36ka-415vac-3-poles-ma-trip-unit-12-5a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F3MA013/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F3MA013","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F3MA013 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}