{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F3MA100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F3MA100","canonicalUrl":"https://aoctrl.com/schneider/C10F3MA100","factsUrl":"https://aoctrl.com/api/mcp/products/C10F3MA100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX NSX100F, circuit breaker, 100A, MA magnetic trip unit, 3P, 36 kA Icu at 415 V AC, toggle control, EN/IEC 60947-2.","salesMarkdown":"## Motor protection breaker with magnetic-only trip It is designed specifically for motor protection, providing short-circuit protection (magnetic) without thermal overload elements — the overload protection is delegated to a separate motor starter or thermal relay upstream. The breaker carries an F breaking capacity code, delivering 36 kA Icu at 380/415 V AC and 85 kA Icu at 220/240 V AC per IEC 60947-2. It is also certified for isolation per EN/IEC 60947-2, meaning it can safely disconnect a motor circuit for maintenance. At 440 V AC the rating drops to 35 kA, and at 690 V AC it falls to 8 kA — so for 690 V applications the available fault current must be verified against that lower limit. The breaker also carries UL 60947-4-1 ratings: 85 kA at 240 V AC, 25 kA at 480 V AC, and 10 kA at 600 V AC, which covers North American motor branch circuits. The MA trip unit is category A (no intentional short-time delay), so full selectivity with downstream devices requires careful coordination study. ## Physical integration and environment The 35 mm connection pitch is standard for ComPacT busbar systems. ## Endurance and dissipation Mechanical endurance is rated at 50,000 cycles. Electrical endurance depends on switching voltage and current: 50,000 cycles at 440 V at half rated current (In/2), 30,000 cycles at 440 V at full In, and 10,000 cycles at 690 V at full In. Power dissipation per pole is 5.2 W, totaling 15.6 W for the three-pole breaker at rated load — a figure to include in thermal calculations for enclosed panels. Ambient operating range is 0–95 % relative humidity, non-condensing.","metaTitle":"Schneider Electric C10F3MA100 ComPacT NSX100F, 100A MA Trip,","metaDescription":"Schneider Electric C10F3MA100 ComPacT NSX100F circuit breaker. 100A magnetic-only MA trip unit, 36 kA Icu at 415 V AC. Motor protection, EN/IEC 60947-2. Available to order, quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10F3MA100","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 3 poles, MA trip unit 100A","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"MA","Number of slots":"5 slot(s)","Protection type":"I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 65 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 65 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"5.2 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"I","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Instantaneous protection pick-up adjustment type Ii":"Adjustable 9 settings","[Isd] Short-time protection pick-up adjustment range":"6...14 x In","[Ii] instantaneous protection pick-up adjustment range":"6...14 x In"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$303.69 – $412.13","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/590c08141a01f07073815d8829d66064.pdf","sourceUrl":"https://www.se.com/th/en/product/C10F3MA100/circuit-breaker-compact-nsx100f-36ka-415vac-3-poles-ma-trip-unit-100a/"},"ai":{"faq":[{"question":"Where can I buy C10F3MA100 and how do I get a price?","answer":"The C10F3MA100 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the closest alternative to C10F3MA100 in the ComPacT NSX family?","answer":"The closest alternative within the same frame is the C10F3MA100 itself — the MA trip unit is specific to motor protection. If a different trip rating is needed, the NSX100F frame accepts interchangeable MA trip units in ratings from 1.5 A to 100 A. For a thermal-magnetic version (motor + cable protection), the TMD trip unit series would be the functional alternative, but that changes the protection curve and application."},{"question":"What compliance documentation does Schneider provide for C10F3MA100?","answer":"The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries suitability for isolation per EN/IEC 60947-2. Standard documentation includes the IEC declaration of conformity, UL recognition, and CE marking. RoHS and REACH compliance are standard for current-production Schneider catalog items."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F3MA100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F3MA100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}