{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F44B100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F44B100","canonicalUrl":"https://aoctrl.com/schneider/C10F44B100","factsUrl":"https://aoctrl.com/api/mcp/products/C10F44B100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX NSX100F, MCCB, 100 A, 4P, 36 kA Icu at 415 V AC, MicroLogic 4.2 AB electronic trip unit with integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C10F44B100 is a ComPacT NSX100F molded-case circuit breaker, 4-pole, rated 100 A at 40 °C with an electronic MicroLogic 4.2 AB trip unit. The 4.2 AB trip gives you L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection all in one device, so you cover both overcurrent and ground-fault from a single breaker. This is a Category A breaker (no intentional short-time delay for selectivity with downstream devices), so it's suited for feeder duty where you need fast clearing rather than cascaded coordination. The C10F44B100 delivers 85 kA Icu at 240 V AC, 36 kA at 415 V, 35 kA at 440 V, and 22 kA at 525 V AC. At 480 V it is rated 25 kA Icu per UL 60947-4-1. Front-connect both top and bottom, which keeps wiring accessible in a panel. The 4-pole format with neutral on the left is standard for European distribution.","metaTitle":"Schneider Electric C10F44B100 ComPacT NSX100F, 100 A, 4P, 36","metaDescription":"Schneider Electric C10F44B100 ComPacT NSX100F MCCB. 100 A, 4P, 36 kA Icu at 415 V AC. MicroLogic 4.2 AB trip unit with earth-leakage. EN/IEC 60947-2. Current lifecycle. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Special application","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3,392.82","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2d13ece227a817724a0a301700a9beb4.pdf","sourceUrl":"https://www.se.com/nl/en/product/C10F44B100/circuit-breaker-compact-nsx100f-36ka-415vac-4-poles-micrologic-vigi-4-2ab-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F44B100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F44B100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F44B100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}