{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F44V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F44V100","canonicalUrl":"https://aoctrl.com/schneider/C10F44V100","factsUrl":"https://aoctrl.com/api/mcp/products/C10F44V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, C10F44V100 NSX100F MCCB, 100 A at 40 °C, 85 kA Icu at 240 V AC, 4P, MicroLogic 4.2 electronic trip unit, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C10F44V100 is a ComPacT NSX100F moulded-case circuit breaker (MCCB) rated 100 A at 40 °C, with a breaking capacity code F delivering 36 kA Icu at 415 V AC per IEC 60947-2. It is a 4-pole unit with an electronic MicroLogic 4.2 trip unit that provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection in a single package. At the more common 480 V AC, it still holds 25 kA Icu per UL 60947-4-1, covering most North American industrial distribution applications. Integrated earth-leakage protection (R function) eliminates the need for a separate RCD or GFCI module downstream, saving one DIN-width slot in the panel and one wiring step. ## Mounting and integration into a panel Mounts on a backplate (not DIN rail) in either horizontal or vertical orientation, flat on the back. Dimensions are 161 mm high by 140 mm wide by 86 mm deep. Front connections both top and bottom, with a 35 mm connection pitch. IP40 front face protection keeps out tools and fingers; IK07 impact rating means it survives accidental hammer knocks during panel build. Toggle handle for manual switching. The OFF position is reached via the IΔn rotary switch for earth-leakage testing. Five accessory slots are available for shunt trips, auxiliary contacts, or under-voltage releases — plan those before wiring to avoid rework.","metaTitle":"Schneider C10F44V100 ComPacT NSX100F, 100A, 85kA, 4P","metaDescription":"Schneider Electric C10F44V100 ComPacT NSX100F MCCB, 100 A at 40 °C, 85 kA Icu at 240 V AC, 4 poles, MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection. In","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"5.8 W N 5.8 W L1 and L3 4.9 W L2","Protected poles description":"4D 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"40...100 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,127.44","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/473b4103811e95c7cf37fe8292b5e333.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10F44V100/circuit-breaker-compact-nsx100f-36ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F44V100/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of C10F44V100?","answer":"Rated 100 A at 40 °C, 4 poles, breaking capacity code F (36 kA Icu at 415 V AC per IEC 60947-2, 85 kA Icu at 240 V AC). Electronic MicroLogic 4.2 trip unit with L, So, I, and integrated earth-leakage protection."},{"question":"Where can I buy C10F44V100?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."},{"question":"What compliance standards does C10F44V100 meet?","answer":"Designed and tested to EN/IEC 60947-2. Pollution degree 3 per IEC 60664-1, overvoltage category IV. IP40 per IEC 60529, IK07 per IEC 62262."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F44V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F44V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}