{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F47E040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F47E040","canonicalUrl":"https://aoctrl.com/schneider/C10F47E040","factsUrl":"https://aoctrl.com/api/mcp/products/C10F47E040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 4P, 40 A, MicroLogic 7.2 E electronic trip unit, 85 kA Icu at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"The C10F47E040 is a ComPacT NSX100F frame circuit breaker with a 40 A MicroLogic 7.2 E electronic trip unit — that 40 A rating is at 40 °C ambient, so if your panel runs hotter you'll need to derate per the thermal curve in the IEC 60947-2 standard it's built to. The 85 kA Icu at 240 V AC means it can safely interrupt a fault of that magnitude without blowing up upstream; at 480 V AC it still holds 25 kA Icu under UL 60947-4-1. ## Trip unit and protection logic The MicroLogic 7.2 E gives you L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection — all adjustable via the LCD display and toggle control. The electronic trip unit keeps the protection curves tighter than a thermal-magnetic breaker, which matters when you're coordinating downstream feeders. Front connections top and bottom, neutral on the left. Overvoltage category IV tells you it's designed for the mains entrance, not downstream subpanels. ## Where it's used and how it lasts This is a distribution breaker — it's the main or feeder in a panel feeding lighting, small motor loads, or general power. Category A utilization means it's not intended for motor starting duty (no dedicated overload relay in the breaker itself). Electrical durability is 50,000 cycles at half rated current, 30,000 at full 40 A, and 10,000 at 690 V — so it'll outlast most panels it's bolted into. Mechanical durability is 50,000 cycles.","metaTitle":"Schneider Electric C10F47E040 ComPacT NSX 40 A, 85 kA Icu","metaDescription":"Schneider Electric C10F47E040 ComPacT NSX circuit breaker, 40 A MicroLogic 7.2 E trip unit, 85 kA Icu at 240 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,589.56 – $3,475.44","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7835a141fda869fbb48c683090dd8031.pdf","sourceUrl":"https://www.se.com/za/en/product/C10F47E040/circuit-breaker-compact-nsx100f-36ka-415vac-4-poles-micrologic-vigi-7-2e-trip-unit-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F47E040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F47E040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F47E040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}