{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F4D","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F4D","canonicalUrl":"https://aoctrl.com/schneider/C10F4D","factsUrl":"https://aoctrl.com/api/mcp/products/C10F4D","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX DC basic frame, NSX100F DC, 100 A at 40 °C, 36 kA Icu at 750 V DC 3P, 4 poles, without trip unit.","salesMarkdown":"The C10F4D is a Schneider Electric ComPacT NSX DC basic frame, designated NSX100F DC, rated 100 A at 40 °C with a 36 kA breaking capacity at 750 V DC across three poles. It is a 4-pole fixed-mount frame without a trip unit, intended for DC distribution applications per IEC 60947-2. ## Breaking capacity and DC ratings The 36 kA Icu holds across the full DC voltage range: 250 V DC single-pole, 500 V DC two-pole, and 750 V DC three-pole. The Ics (service breaking capacity) matches the Icu at each voltage, meaning the breaker can be reclosed after a fault at full rated current without derating — a key spec for DC bus protection where fault currents are sustained. Rated operational voltage is 750 V DC, with insulation voltage also 750 V DC. ## Physical integration and mounting Fixed backplate mounting, 140 mm wide by 161 mm high by 86 mm deep. IP40 front face, IK07 impact resistance — standard for enclosed distribution boards. Listed as current production. This is a basic frame — no trip unit included — so the buyer must pair it with a compatible electronic or thermal-magnetic trip unit (e.g., Schneider Micrologic series) to complete the breaker.","metaTitle":"C10F4D ComPacT NSX100F DC 100A 36kA DC 4P Basic Frame","metaDescription":"C10F4D ComPacT NSX100F DC basic frame, 100A rated, 36 kA breaking capacity at 750 V DC, 4 poles, without trip unit. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"DC","Product name":"ComPacT NSX DC","Mounting mode":"Fixed","Protection type":"Without protection","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Breaking capacity":"36 kA Icu at 250 V DC 1P conforming to IEC 60947-2 36 kA Icu at 24...125 V DC 1P conforming to IEC 60947-2 36 kA Icu at 500 V DC 2P conforming to IEC 60947-2 36 kA Icu at 750 V DC 3P conforming to IEC 60947-2","Device short name":"NSX100F DC","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Utilisation category":"Category A","Electrical durability":"10000 cycles 250 V DC In/2 conforming to IEC 60947-2 10000 cycles 500 V DC In/2 conforming to IEC 60947-2 10000 cycles 750 V DC In/2 conforming to IEC 60947-2 5000 cycles 250 V DC In conforming to IEC 60947-2 5000 cycles 500 V DC In conforming to IEC 60947-2 5000 cycles 750 V DC In conforming to IEC 60947-2","Maximum breaking time":"10 ms","Mechanical durability":"10000 cycles conforming to IEC 60947-2","Breaking capacity code":"F 36 kA 750 V DC","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP40 conforming to IEC 60529","Product or component type":"Basic frame","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","[Ui] rated insulation voltage":"750 V DC conforming to IEC 60947-2","[Ue] rated operational voltage":"750 V DC conforming to IEC 60947-2","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"36 kA at 250 V DC conforming to IEC 60947-2 (1P) 36 kA at 24...125 V DC conforming to IEC 60947-2 (1P) 36 kA at 500 V DC conforming to IEC 60947-2 (2P) 36 kA at 750 V DC conforming to IEC 60947-2 (3P)","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$179.28 – $280.75","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8da61057b99ac9da68bba13855955ff9.pdf","sourceUrl":"https://www.se.com/ie/en/product/C10F4D/circuit-breaker-basic-frame-compact-nsx100f-dc-36ka-750vdc-4-poles-100a-frame-rating-without-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F4D/alternatives.json"},"ai":{"faq":[{"question":"What is C10F4D used for?","answer":"It is a basic frame for a DC molded-case circuit breaker, rated 100 A at 40 °C with 36 kA breaking capacity at up to 750 V DC, used in DC distribution applications per IEC 60947-2."},{"question":"Where can I buy C10F4D?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does this brand provide for C10F4D?","answer":"The breaker is designed and tested to EN/IEC 60947-2, with overvoltage category III and pollution degree 3 per IEC 60664-1. For specific RoHS, REACH, or UL documentation, request the manufacturer's compliance declaration at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F4D","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F4D when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}