{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F4TM025","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F4TM025","canonicalUrl":"https://aoctrl.com/schneider/C10F4TM025","factsUrl":"https://aoctrl.com/api/mcp/products/C10F4TM025","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 4P, 25 A, TM-D trip unit, 85 kA Icu at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"The TM-D gives you fixed thermal overload (L) and fixed magnetic short-circuit (I) protection — no adjustment dials, no interchangeable rating plugs. At 480 V AC (common for North American distribution) it still holds 25 kA Icu, and at 600 V AC it drops to 10 kA Icu. Mounts on a backplate — no DIN-rail adapter here. Four poles, neutral on the left, front-facing connections top and bottom. The 140 mm width and 161 mm height fit the standard ComPacT NSX cutout; the 86 mm depth leaves room for cable bending behind the panel door. Compliance documentation is straightforward: the breaker carries EN/IEC 60947-2 certification, which covers the essential safety and performance requirements for low-voltage switchgear. IP40 front face keeps tools and fingers out; the back and sides rely on the enclosure's own IP rating. Backplate-mounted, four-pole, front-connected. Five accessory slots on the front accept auxiliary contacts, shunt trips, under-voltage releases, or motor operators — the slots are shared, so you plan the accessory count before wiring. Horizontal or vertical mounting, flat on the backplate — no derating required for orientation. The IK07 impact rating means it survives a 2 J hammer blow (tool drop during commissioning) without the case cracking. 50,000 mechanical cycles and 30,000 electrical cycles at rated current (440 V, In) give a realistic service life for a distribution breaker that isn't switched daily.","metaTitle":"Schneider Electric C10F4TM025 ComPacT NSX100F, 25 A, 85 kA","metaDescription":"Schneider Electric C10F4TM025 ComPacT NSX100F circuit breaker, 25 A thermal-magnetic TM-D trip, 85 kA Icu at 240 V AC. EN/IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"25 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"25 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"1 x Ir (4D)","Power dissipation per pole":"4.01 W","Protected poles description":"4D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"300 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$197.01 – $547.78","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ca879abbec2dd3cd0144ebc7f523b34c.pdf","sourceUrl":"https://www.se.com/nl/en/product/C10F4TM025/circuit-breaker-compact-nsx100f-36ka-415vac-4-poles-4d-neutral-fully-protected-tmd-trip-unit-25a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F4TM025/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to C10F4TM025 in the same family?","answer":"Within the ComPacT NSX100F frame, the only difference between order codes is the trip unit rating and the trip technology. A 32 A TM-D (C10F4TM032) or a 25 A Micrologic 2.2 electronic trip (C10F4D025) share the same physical footprint, breaking capacity, and accessory compatibility — the choice is purely the protection curve and adjustability you need."},{"question":"What compliance documentation does this breaker carry?","answer":"It is certified to EN/IEC 60947-2, rated for pollution degree 3 per IEC 60664-1, and carries an IP40 front-face protection rating. Suitability for isolation is confirmed per EN/IEC 60947-2."},{"question":"Where can I buy C10F4TM025 and how is it quoted?","answer":"Sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F4TM025","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F4TM025 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}