{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F4TM032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F4TM032","canonicalUrl":"https://aoctrl.com/schneider/C10F4TM032","factsUrl":"https://aoctrl.com/api/mcp/products/C10F4TM032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, thermal-magnetic circuit breaker, 32 A, 4P, 85 kA Icu at 240 V AC, Type F breaking capacity.","salesMarkdown":"The Schneider Electric C10F4TM032 is a ComPacT NSX100F circuit breaker with a 32 A thermal-magnetic TM-D trip unit, 4 poles, and an F breaking capacity code — meaning 36 kA Icu at 380/415 V AC. It's rated 85 kA Icu at 220/240 V AC and still delivers 22 kA Icu at 525 V AC, so it covers both light commercial and heavy industrial distribution panels without swapping frames. The TM-D trip unit gives you L (thermal overload) and I (magnetic short-circuit) protection, with the neutral protection set at 1 x Ir for a 4D configuration. That means the breaker tracks overload on all four poles equally — no derating guesswork when you land a balanced 3-phase plus neutral feed. Mechanical durability is rated at 50,000 cycles, with electrical durability ranging from 50,000 cycles at 440 V In/2 down to 10,000 cycles at 690 V In. For a panel that sees regular switching — like a pump start/stop or a conveyor section — that's a solid service life before you're pulling a replacement. The 140 mm width and 161 mm height give it a footprint that matches standard ComPacT NSX panel cutouts, and the 35 mm connection pitch lines up with common busbar systems and terminal blocks. Front connections on both the line and load sides mean you can bus it in a panel without flipping the breaker or adding awkward right-angle adapters. The toggle control is right there on the front — no pushbutton or rotary handle to confuse a maintenance crew pulling a lockout. ## Environmental and compliance specs that matter for the install IP40 enclosure protection keeps dust and fingers out, and the IK07 impact rating means it'll survive a tool bump in a crowded panel. Operating altitude goes to 2000 m without derating, and up to 5000 m with derating — worth checking if your site sits above a mile high. Compliant with EN/IEC 60947-2 and suitable for isolation per that standard, so it doubles as a visible-break disconnect when the toggle is in the OFF position. No separate isolator needed on the load side for most code jurisdictions.","metaTitle":"Schneider Electric C10F4TM032 ComPacT NSX100F, 32 A, 4P, 85","metaDescription":"Schneider Electric C10F4TM032 ComPacT NSX circuit breaker. 32 A TM-D trip unit, 4-pole, 85 kA Icu at 240 V AC. Active production. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"32 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"32 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"1 x Ir (4D)","Power dissipation per pole":"4.03 W","Protected poles description":"4D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"400 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$425.57 – $547.78","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/333f490499c03e71c08178a15ea0803a.pdf","sourceUrl":"https://www.se.com/sg/en/product/C10F4TM032/circuit-breaker-compact-nsx100f-36ka-at-415vac-tmd-trip-unit-32a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F4TM032/alternatives.json"},"ai":{"faq":[{"question":"What is C10F4TM032's breaking capacity at 415 V?","answer":"At 380/415 V AC, the C10F4TM032 delivers 36 kA Icu per IEC 60947-2, which is the F breaking capacity code rating."},{"question":"What compliance standards does C10F4TM032 meet?","answer":"The C10F4TM032 is compliant with EN/IEC 60947-2 and is suitable for isolation per that standard. It carries IP40 and IK07 ratings, pollution degree 3, and overvoltage category III."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F4TM032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F4TM032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}