{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F4TM032C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F4TM032C","canonicalUrl":"https://aoctrl.com/schneider/C10F4TM032C","factsUrl":"https://aoctrl.com/api/mcp/products/C10F4TM032C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100F, 4-pole 32 A thermal-magnetic MCCB, 85 kA Icu at 240 V, 36 kA Icu at 415 V, TM-D trip unit, IP40, backplate mount.","salesMarkdown":"## What a 32 A TM-D MCCB means for your panel That TM-D means it gives you overload protection (thermal element) and short-circuit protection (magnetic element) in one package, no separate relay or CT needed. The 32 A rating is at 50 °C, so if your panel runs hotter than that, you'll want to check the derating curve in the IEC 60947-2 documentation. ## Breaking capacity: what the F code gets you Mounts to a backplate, not a DIN rail — so you'll need a panel-mounting kit or a mounting plate drilled for the 140 mm width and 161 mm height. Connections are front-facing both top and bottom, which makes wiring and inspection straightforward in a row of breakers. The toggle handle gives clear visual indication of tripped vs on/off state.","metaTitle":"C10F4TM032C ComPacT NSX100F 32A 4P Thermal-Magnetic, 36kA 41","metaDescription":"C10F4TM032C Schneider ComPacT NSX100F 32A 4P MCCB, 85kA at 240V, 36kA at 415V, TM-D thermal-magnetic trip, IP40, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"32 A at 50 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"32 A at 50 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"1 x Ir (4D)","Power dissipation per pole":"4.03 W","Protected poles description":"4D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"400 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/005d6566380c4a99bf25ac078a95711a.pdf","sourceUrl":"https://www.se.com/ae/en/product/C10F4TM032C/circuit-breaker-compact-nsx100f-36ka-at-415vac-tmd-trip-unit-32a-50-degrees-c-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F4TM032C/alternatives.json"},"ai":{"faq":[{"question":"What is C10F4TM032C's breaking capacity at 415 V?","answer":"36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That's the F breaking capacity code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F4TM032C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F4TM032C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}