{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F4TM063","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F4TM063","canonicalUrl":"https://aoctrl.com/schneider/C10F4TM063","factsUrl":"https://aoctrl.com/api/mcp/products/C10F4TM063","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, 63 A, 4P, TM-D trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C10F4TM063 is a ComPacT NSX100F frame circuit breaker with a 63 A thermal-magnetic TM-D trip unit, 4 poles, and an F breaking capacity code — meaning 36 kA Icu at 415 V AC. That 36 kA interrupting rating at 415 V is the figure that governs selectivity coordination in a 400 V distribution board; the breaker also carries 85 kA Icu at 240 V and 25 kA at 480 V (UL 60947-4-1), so it slots into both IEC and UL-labeled installations without a separate SCCR derate for the same frame. Front connections both upside and downside; connection pitch is 35 mm. The 4-pole version with neutral on the left (fixed position) fits standard 140 mm wide panel cutouts. ## Durability and environmental limits Mechanical endurance is 50,000 cycles; electrical endurance at 440 V rated current is 30,000 cycles — enough for frequent switching in a distribution board feeding motor loads or lighting contactors. IP40 enclosure rating and IK07 impact resistance handle typical panel environments; relative humidity up to 95% is accommodated without derating. Operating altitude to 2000 m without derating, with derating curves above that.","metaTitle":"Schneider Electric C10F4TM063 ComPacT NSX 63A 4P Circuit Bre","metaDescription":"Schneider Electric C10F4TM063 ComPacT NSX circuit breaker. 63 A thermal-magnetic TM-D trip unit, 4 poles, 36 kA Icu at 415 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"63 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"63 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"1 x Ir (4D)","Power dissipation per pole":"8.61 W","Protected poles description":"4D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$200.90 – $547.78","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/743bcb46ffdd329aaf6b84d5e3d62281.pdf","sourceUrl":"https://www.se.com/nl/en/product/C10F4TM063/circuit-breaker-compact-nsx100f-36ka-415vac-4-poles-4d-neutral-fully-protected-tmd-trip-unit-63a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F4TM063/alternatives.json"},"ai":{"faq":[{"question":"What is C10F4TM063's breaking capacity at 415 V?","answer":"The C10F4TM063 carries 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2."},{"question":"What compliance documentation does this brand provide for C10F4TM063?","answer":"The C10F4TM063 is certified to EN/IEC 60947-2 and UL 60947-4-1, with suitability for isolation per those standards. Pollution degree 3 per IEC 60664-1 and overvoltage category III are documented."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F4TM063","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F4TM063 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}