{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F6TM016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F6TM016","canonicalUrl":"https://aoctrl.com/schneider/C10F6TM016","factsUrl":"https://aoctrl.com/api/mcp/products/C10F6TM016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, 4P, 16 A at 40 °C, thermal-magnetic trip unit TM-D, breaking capacity 85 kA Icu at 240 V AC, 36 kA at 415 V AC.","salesMarkdown":"The thermal-magnetic curve gives L (thermal overload) and I (magnetic short-circuit) protection — no electronic adjustment, no earth-leakage module, just a reliable bimetal-and-solenoid pair. The 50,000-cycle mechanical durability and 50,000-cycle electrical durability at 440 V In/2 tell you this breaker is built for a panel that cycles, not just a disconnect that sits closed. The IP40 front face keeps tools and fingers out; the IK07 impact rating handles a 2 J hammer blow — enough for a panel door that gets bumped during maintenance. ## Integration notes Mounts flat on a backplate — no DIN-rail adapter needed for this frame. The 140 mm width and 161 mm height fit the standard NSX100F cutout. Front connections top and bottom simplify busbar or cable landing. Neutral is on the left; the toggle control is manual only — no motor operator or rotary handle in this variant. ## Altitude and environment Above that, up to 5000 m, you'll need to derate — the thinner air reduces the arc-quenching efficiency. The 0–95 % relative humidity range covers everything from a dry control room to a humid coastal plant without condensation protection.","metaTitle":"C10F6TM016 ComPacT NSX100F 16A 4P MCCB, 85 kA Icu at 240V","metaDescription":"C10F6TM016 is a Schneider Electric ComPacT NSX100F 16A thermal-magnetic MCCB. 4P, 85 kA Icu at 240 V AC. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"16 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"16 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D)","Power dissipation per pole":"2.92 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"190 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$179.96 – $535.57","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d285ca3ec5f1ae6ccc4260ef161716b9.pdf","sourceUrl":"https://www.se.com/ph/en/product/C10F6TM016/circuit-breaker-compact-nsx100f-36ka-at-415vac-tmd-trip-unit-16a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F6TM016/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C10F6TM016 and how do I get a price?","answer":"The part is sourced to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time."},{"question":"What is C10F6TM016's breaking capacity at 415 V?","answer":"36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2."},{"question":"Does C10F6TM016 include earth-leakage protection?","answer":"No, the listing specifies earth-leakage protection as 'Without'. This is a straight thermal-magnetic breaker with no add-on Vigi module."},{"question":"What compliance documentation does this brand provide for C10F6TM016?","answer":"The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. The IP and IK ratings are per IEC 60529 and IEC 62262. Specific RoHS/REACH declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F6TM016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F6TM016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}