{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F6TM032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F6TM032","canonicalUrl":"https://aoctrl.com/schneider/C10F6TM032","factsUrl":"https://aoctrl.com/api/mcp/products/C10F6TM032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100F, 4P, 32 A thermal-magnetic circuit breaker, 85 kA Icu at 240 V AC, toggle control, front connections.","salesMarkdown":"The Schneider Electric C10F6TM032 is a ComPacT NSX100F 4-pole circuit breaker with a 32 A thermal-magnetic TM-D trip unit. It is rated for distribution applications and provides overload (thermal) and short-circuit (magnetic) protection per EN/IEC 60947-2. The breaking capacity reaches 85 kA Icu at 240 V AC and 36 kA Icu at 415 V AC, making it suitable for high-fault panels where the upstream transformer can deliver substantial short-circuit current. The 32 A rating at 40 °C is the continuous current the breaker can carry without tripping in a 40 °C ambient. The TM-D trip unit uses a thermal bimetal for overload and a magnetic coil for short-circuit — no electronic adjustment, so it is a fixed-curve device. The 85 kA Icu at 240 V AC is the maximum fault current it can safely interrupt at that voltage; at 415 V AC the rating drops to 36 kA Icu, which still covers most commercial and light industrial panelboards. Front connections on both the line and load sides simplify busbar or cable routing in a panel. The 140 mm width and 161 mm height fit standard ComPacT NSX cutouts; depth is 86 mm. The toggle control provides a clear visual position indicator.","metaTitle":"Schneider Electric C10F6TM032 ComPacT NSX100F, 32 A, 85 kA","metaDescription":"Schneider Electric C10F6TM032 ComPacT NSX circuit breaker, 32 A thermal-magnetic TM-D trip unit, 85 kA Icu at 240 V AC, EN/IEC 60947-2. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"32 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"32 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D)","Power dissipation per pole":"4.03 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"400 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$183.18 – $534.01","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/eb4db94271addf1be86d8a6f45ce7170.pdf","sourceUrl":"https://www.se.com/za/en/product/C10F6TM032/circuit-breaker-compact-nsx100f-36ka-at-415vac-tmd-trip-unit-32a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F6TM032/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C10F6TM032?","answer":"The C10F6TM032 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for C10F6TM032?","answer":"The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. The IP degree is IP40, and the IK degree is IK07 per IEC 62262. Pollution degree 3 per IEC 60664-1 is specified."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F6TM032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F6TM032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}