{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F6TM040C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F6TM040C","canonicalUrl":"https://aoctrl.com/schneider/C10F6TM040C","factsUrl":"https://aoctrl.com/api/mcp/products/C10F6TM040C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 40 A, 4P, TM-D trip unit, 36 kA Icu at 415 V AC, toggle control.","salesMarkdown":"The C10F6TM040C is a Schneider Electric ComPacT NSX100F moulded-case circuit breaker with a 40 A thermal-magnetic TM-D trip unit, four poles, and a 36 kA interrupting capacity at 415 V AC. The 40 A rating at 50 °C covers typical lighting, small motor, or general distribution loads without derating in a warm enclosure. At 220/240 V it jumps to 85 kA Icu, and at 690 V it still holds 8 kA Icu. That spread means the same breaker can be used across different voltage levels in the same plant without swapping frames. The utilisation category A (non-selectivity-oriented) means it's designed to clear faults fast rather than coordinate with downstream devices — fine for a main or branch breaker where you want quick trip, not for a selective main where you need time delay. Mounts flat on a backplate — no DIN rail here. The 140 mm width and 161 mm height fit standard MCCB cutouts in distribution boards. IP40 front face keeps out tools and fingers; IK07 impact rating means it survives a 2 J hammer blow — fine for a locked electrical room but not for a washdown area. ## Durability and duty cycles Rated for 50,000 mechanical operations and 30,000 electrical cycles at rated current (40 A, 440 V). That's a solid 10+ years of daily switching in a machine-tool or conveyor application. At half rated current (20 A) the electrical endurance doubles to 50,000 cycles — typical for lightly loaded feeder breakers that cycle with the shift schedule.","metaTitle":"Schneider Electric C10F6TM040C ComPacT NSX 40A MCCB, 36kA 41","metaDescription":"Schneider Electric C10F6TM040C ComPacT NSX100F MCCB, 40A thermal-magnetic TM-D trip, 36kA Icu at 415V AC. Current lifecycle, available to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"40 A at 50 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"40 A at 50 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D)","Power dissipation per pole":"5.47 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/12ce156f8f20f98807529ef76aff73c8.pdf","sourceUrl":"https://www.se.com/ae/en/product/C10F6TM040C/circuit-breaker-compact-nsx100f-36ka-at-415vac-tmd-trip-unit-40a-50-degrees-c-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F6TM040C/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C10F6TM040C and get a price?","answer":"This part is sourced to order against an RFQ through independent industrial distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of C10F6TM040C at 415 V?","answer":"36 kA Icu at 380/415 V AC, 50/60 Hz, per IEC 60947-2. At 440 V it's 35 kA; at 500 V it's 25 kA."},{"question":"What compliance documentation does this breaker carry?","answer":"It meets EN/IEC 60947-2, is suitable for isolation per that standard, and carries IP40 and IK07 ratings. Pollution degree 3 per IEC 60664-1. No earth-leakage protection built in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F6TM040C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F6TM040C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}