{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F6TM050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F6TM050","canonicalUrl":"https://aoctrl.com/schneider/C10F6TM050","factsUrl":"https://aoctrl.com/api/mcp/products/C10F6TM050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, 4P, 50 A, TM-D trip unit, 36 kA Icu at 415 V AC, IP40, toggle control.","salesMarkdown":"The TM-D trip provides fixed thermal protection for overloads (L) and fixed magnetic protection for short circuits (I); no adjustment dials, which simplifies specification but means you select the exact amp rating for the load. Breaking capacity is the headline: 85 kA Icu at 240 V AC, 36 kA Icu at 415 V AC, and 35 kA at 440 V AC, all per IEC 60947-2. Rated for isolation per EN/IEC 60947-2, meaning it provides a visible-break isolation point when open — no separate disconnect switch needed upstream in many configurations. IP40 enclosure protection keeps tools and fingers out but not water; mount in a cabinet, not exposed. Front connection both top and bottom simplifies busbar or cable routing in a switchboard. The 4-pole version (3D neutral protection — no protection on the neutral pole) fits standard 140 mm wide cutouts; depth is 86 mm, height 161 mm. Connection pitch of 35 mm matches common busbar systems. Electrical durability: 50,000 cycles at 440 V at half rated current, 30,000 cycles at full rated current. Mechanical durability is 50,000 cycles. For a distribution breaker these are high — it handles frequent switching if used as a manual disconnect, not just a backup overcurrent device.","metaTitle":"Schneider Electric C10F6TM050 ComPacT NSX 50A MCCB, 36kA 415","metaDescription":"Schneider Electric C10F6TM050 ComPacT NSX circuit breaker, 50A thermal-magnetic TM-D trip, 4P, 36 kA Icu at 415 V AC. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"50 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"50 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D)","Power dissipation per pole":"4.11 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$289.17 – $535.57","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4febd589a126eb6cda0eafbe676c0e87.pdf","sourceUrl":"https://www.se.com/vn/en/product/C10F6TM050/circuit-breaker-compact-nsx100f-36ka-415vac-4-poles-3d-neutral-not-protected-tmd-trip-unit-50a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F6TM050/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for C10F6TM050?","answer":"50 A thermal-magnetic trip (TM-D), 4 poles, breaking capacity 36 kA Icu at 415 V AC (F code), rated for isolation per IEC 60947-2, IP40, pollution degree 3."},{"question":"What standards does C10F6TM050 comply with?","answer":"It complies with EN/IEC 60947-2 for circuit breakers, IEC 60664-1 for pollution degree, and IEC 62262 for IK07 impact resistance. It is suitable for isolation per EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F6TM050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F6TM050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}