{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F6TM050C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F6TM050C","canonicalUrl":"https://aoctrl.com/schneider/C10F6TM050C","factsUrl":"https://aoctrl.com/api/mcp/products/C10F6TM050C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, 4P, 50 A thermal-magnetic TM-D trip, 36 kA Icu at 415 V AC, toggle control, backplate mount.","salesMarkdown":"It is a 4-pole device rated for distribution applications, with a breaking capacity of 36 kA Icu at 415 V AC (50/60 Hz) per IEC 60947-2. The F breaking-capacity code means it delivers 36 kA at 415 V — the most common industrial low-voltage fault level — so it handles the majority of panelboard and sub-distribution duties without needing a higher-rated frame. At 440 V AC the Icu is 35 kA, at 500 V it drops to 25 kA, and at 690 V it is 8 kA — so the voltage class of your system determines whether this breaker clears a fault without damage. Electrical durability is 50,000 cycles at 440 V at half rated current (In/2), 30,000 cycles at full In, and 10,000 cycles at 690 V full In. Mechanical durability is 50,000 cycles. For a distribution breaker in a panel that sees infrequent switching (a main or feeder), this is ample; for a machine-tool disconnect cycled multiple times per shift, the electrical endurance at full load is the number to watch. The IP40 enclosure rating keeps out tools and wires >1 mm; the IK07 impact rating means it withstands a 2 J hammer blow to the front face. Neutral is on the left; the neutral protection setting is 3D (no protection) — if you need a fully protected neutral, this is not the variant.","metaTitle":"C10F6TM050C ComPacT NSX 50A MCCB, 36kA 415V AC, TM-D Trip","metaDescription":"C10F6TM050C ComPacT NSX circuit breaker, 50A thermal-magnetic TM-D trip unit, 36kA breaking capacity at 415V AC. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"50 A at 50 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"50 A at 50 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D)","Power dissipation per pole":"4.11 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e1baa480e7879ba2626f67df93600eab.pdf","sourceUrl":"https://www.se.com/ae/en/product/C10F6TM050C/circuit-breaker-compact-nsx100f-36ka-at-415vac-tmd-trip-unit-50a-50-degrees-c-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F6TM050C/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C10F6TM050C at 415 V?","answer":"36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the F breaking-capacity code rating, which covers the most common industrial fault level."},{"question":"What does the TM-D trip unit protect against?","answer":"L (thermal overload) and I (magnetic short-circuit) protection. The thermal element handles sustained overcurrents; the magnetic element trips instantaneously on high fault currents."},{"question":"Where can I buy C10F6TM050C?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What standards does C10F6TM050C comply with?","answer":"It is designed and tested to EN/IEC 60947-2 for low-voltage switchgear and controlgear. It is also suitable for isolation per that standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F6TM050C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F6TM050C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}