{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F6TM080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F6TM080","canonicalUrl":"https://aoctrl.com/schneider/C10F6TM080","factsUrl":"https://aoctrl.com/api/mcp/products/C10F6TM080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100F, MCCB, 80 A, 4P, TM-D trip, 36 kA Icu at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"Four poles, toggle control, front-connected terminals. This is a current-production part, not an end-of-life line. ## What the breaking capacity means for your panel At 415 V AC, the C10F6TM080 delivers 36 kA Icu per IEC 60947-2. The 140 mm width × 161 mm height × 86 mm depth fits standard panel layouts. Enclosure protection is IP40 (finger-safe, no gasket) and IK07 impact resistance. ## Durability and electrical life Rated for 50,000 mechanical operations and 30,000 electrical cycles at 440 V at rated current (In). At half load (In/2) at 440 V, electrical durability jumps to 50,000 cycles. At 690 V, expect 10,000 cycles at In and 20,000 at In/2. These numbers assume resistive or mixed loads; motor switching or high inrush will reduce service life. Overvoltage category III (distribution-level). Suitable for isolation. Pollution degree 3. The breaking capacities are also listed with UL 60947-4-1 references at 240 V (85 kA), 480 V (25 kA), and 600 V (10 kA), indicating UL recognition for the US market. No earth-leakage protection built in — add a Vigi module if ground-fault protection is required.","metaTitle":"Schneider Electric C10F6TM080 ComPacT NSX MCCB, 80 A, 4P, 36","metaDescription":"Schneider Electric C10F6TM080 ComPacT NSX 80 A 4-pole MCCB with TM-D trip unit. 36 kA Icu at 415 V AC. EN/IEC 60947-2. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"80 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"80 A at 50 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D)","Power dissipation per pole":"8.77 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"640 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$301.59 – $579.47","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/43837375912938d4cd4acdda4f27fde0.pdf","sourceUrl":"https://www.se.com/nl/en/product/C10F6TM080/circuit-breaker-compact-nsx100f-36ka-415vac-4-poles-3d-neutral-not-protected-tmd-trip-unit-80a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F6TM080/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the C10F6TM080 at 415 V?","answer":"36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That is the ultimate breaking capacity — the breaker can safely interrupt one fault at that level."},{"question":"What does the TM-D trip unit protect against?","answer":"Thermal overload (L) via bimetal and magnetic short-circuit (I) via solenoid. Fixed settings — no field adjustment on the trip curve."},{"question":"What is the physical size of the C10F6TM080?","answer":"140 mm wide × 161 mm high × 86 mm deep. Fits standard backplate mounting in horizontal or vertical orientation."},{"question":"Is the C10F6TM080 suitable for isolation?","answer":"Yes, it is marked suitable for isolation per EN/IEC 60947-2, with a visible contact position indicator."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F6TM080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F6TM080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}