{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10F6TM100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10F6TM100","canonicalUrl":"https://aoctrl.com/schneider/C10F6TM100","factsUrl":"https://aoctrl.com/api/mcp/products/C10F6TM100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C10F6TM100, 4P 100A thermal-magnetic MCCB, 36 kA Icu at 415 V AC, toggle control, backplate mount.","salesMarkdown":"The TM-D unit provides L (thermal) overload protection and I (magnetic) short-circuit protection, so it handles motor inrush and distribution feeder duty equally. Breaking capacity is where this part earns its place in the panel. At 415 V AC — the most common industrial distribution voltage — it delivers 36 kA Icu. For a 400 V panel with a transformer upstream that can deliver 35 kA of fault current, this breaker holds coordination without cascading to the main. The 4-pole (4P) configuration with neutral on the left and no integral earth-leakage module means this is a straight distribution or feeder breaker — not a GFCI. Neutral protection is set to 3D (no protection), so the neutral pole is switched but not monitored for overcurrent; confirm your system grounding design before specifying. ## Mounting and integration — backplate, front connections, IP40 Front-facing connections for both line and load sides simplify bus-bar routing and cable entry in a standard panel layout. IP40 and IK07 mean it is protected against tools and wires >1 mm and against 0.5 J impacts — fine for a clean indoor panel, not for washdown zones. Five equipment slots allow auxiliary contacts, shunt trips, or an under-voltage release to be added without removing the breaker from the panel. ## Lifecycle and sourcing — active production, quoted to order Lifecycle status is current — Schneider continues to manufacture the ComPacT NSX range. This is not a phase-out or NRND part. For volume purchases or BOM-line commitments, submit a request with target quantity and delivery window. ## Compliance and approvals — IEC 60947-2, isolation suitability Certified to EN/IEC 60947-2 with utilisation category A — suitable for distribution, not for motor starting under load.","metaTitle":"Schneider Electric C10F6TM100 ComPacT NSX 100A MCCB, 36kA 41","metaDescription":"Schneider Electric C10F6TM100 ComPacT NSX 100A MCCB with TM-D trip unit. 4-pole, 36 kA Icu at 415 V AC. Active production, sourced to order. Quoted against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 50 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D)","Power dissipation per pole":"8.8 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120...400 s at 1.5 x In 15 s at 6 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"0.7...1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"800 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$202.00 – $595.30","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b8de447f082f3523d6b277a9b83ee21f.pdf","sourceUrl":"https://www.se.com/za/en/product/C10F6TM100/circuit-breaker-compact-nsx100f-36ka-at-415vac-tmd-trip-unit-100a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10F6TM100/alternatives.json"},"ai":{"faq":[{"question":"Who supplies C10F6TM100 and how is it quoted?","answer":"Sourced through independent distribution channels. Submit an RFQ with your target quantity and delivery window; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to C10F6TM100 in the ComPacT NSX family?","answer":"Within the ComPacT NSX range, the closest alternative would be a different breaking-capacity code (e.g., an 'N' or 'S' frame) or a different trip-unit rating. The TM-D trip unit and 4-pole configuration are common across the family; the deciding factor is the required Icu at your system voltage."},{"question":"What compliance documentation does Schneider provide for C10F6TM100?","answer":"The breaker is certified to EN/IEC 60947-2 and is suitable for isolation per that standard. Standard Schneider documentation includes a Declaration of Conformity covering the applicable EU directives. For specific RoHS or REACH declarations, request them at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10F6TM100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10F6TM100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}