{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10H3MA003","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10H3MA003","canonicalUrl":"https://aoctrl.com/schneider/C10H3MA003","factsUrl":"https://aoctrl.com/api/mcp/products/C10H3MA003","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX100H, 3-pole MCCB, 2.5 A magnetic-only (MA) trip unit, 100 kA Icu at 240 V AC, IP40, backplate mount.","salesMarkdown":"The Schneider C10H3MA003 is a ComPacT NSX100H molded-case circuit breaker, 3-pole, fitted with a magnetic-only (MA) trip unit rated 2.5 A at 65 °C. It is designed specifically for motor protection — the MA curve provides short-circuit (magnetic) protection only, no thermal overload, relying on a separate motor starter or overload relay for the thermal element. This is standard practice for motor branch circuits where the MCCB clears faults and the overload relay handles running protection. Rated 100 kA Icu at 240 V AC and 70 kA at 415 V AC per IEC 60947-2, this breaker handles high available fault current common in industrial distribution — a 100 kA SCCR at the lower voltage means it can be applied on the secondary side of a large transformer without requiring a current-limiting fuse upstream. At 690 V AC the Icu drops to 10 kA, so verify the system voltage matches the rating. ## Integration notes Mounts on a backplate — no DIN rail. Front-connect terminals top and bottom, 35 mm pole pitch. IP40 enclosure rating (finger-safe), IK07 impact resistance. Pollution degree 3 environment (conductive pollution, typical in industrial panels). Overvoltage category III. Horizontal or vertical orientation allowed, flat on the back.","metaTitle":"Schneider C10H3MA003 ComPacT NSX 100H, 2.5 A MA Trip, 100 kA","metaDescription":"Schneider C10H3MA003 ComPacT NSX100H MCCB, 3-pole, 2.5 A magnetic-only trip unit, 100 kA Icu at 240 V AC. EN/IEC 60947-2. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$340.07 – $558.95","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/60ab1f4b1a98b578f53d4562c797d8d6.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10H3MA003/circuit-breaker-compact-nsx100h-70ka-415vac-3-poles-ma-trip-unit-2-5a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10H3MA003/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10H3MA003","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10H3MA003 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}