{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10H3MA025","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10H3MA025","canonicalUrl":"https://aoctrl.com/schneider/C10H3MA025","factsUrl":"https://aoctrl.com/api/mcp/products/C10H3MA025","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100H, 3P, 25 A magnetic-only trip unit (MA), 70 kA Icu at 415 V AC, toggle control.","salesMarkdown":"## Motor-protection MCCB with magnetic-only trip It is designed specifically for motor protection, where the upstream breaker handles short-circuit faults while the motor starter's overload relay manages thermal protection. The magnetic-only trip responds to fault currents only — no thermal element — so it coordinates cleanly with a separate overload relay downstream. Rated 70 kA Icu at 415 V AC (50/60 Hz) per IEC 60947-2, this H-frame breaker clears high fault currents typical in industrial distribution panels. At 480 V AC the interrupting rating is 65 kA Icu per UL 60947-4-1, making it suitable for North American motor branch circuits as well. The 25 A MA trip unit is sized for motor full-load current, not cable protection. Because it lacks thermal protection, you pair it with a thermal overload relay (e.g., TeSys LR series) set to the motor nameplate FLA. The magnetic pickup is fixed and non-adjustable on the MA trip — it trips instantaneously on short-circuit, leaving the overload relay to handle running overcurrents. In a 480 V panel with a 65 kA available fault current, the C10H3MA025 holds its rating without requiring a current-limiting upstream fuse. The IP40 front face keeps tools and fingers out; the backplate mount and 35 mm connection pitch match standard DIN-rail or direct-panel layouts.","metaTitle":"Schneider Electric C10H3MA025 ComPacT NSX 25A MCCB, 70kA 415","metaDescription":"Schneider Electric C10H3MA025 ComPacT NSX 100H MCCB, 25 A magnetic-only trip unit, 70 kA Icu at 415 V AC. Motor protection, current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$340.07 – $552.58","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f39f799eec21f77e96b19f675c2bfc85.pdf","sourceUrl":"https://www.se.com/ph/en/product/C10H3MA025/circuit-breaker-compact-nsx100h-70ka-at-415vac-ma-trip-unit-25a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10H3MA025/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10H3MA025","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10H3MA025 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}