{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10H3MA050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10H3MA050","canonicalUrl":"https://aoctrl.com/schneider/C10H3MA050","factsUrl":"https://aoctrl.com/api/mcp/products/C10H3MA050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NSX, circuit breaker, C10H3MA050, 3P, 50 A, magnetic trip unit MA, 70 kA at 415 V AC.","salesMarkdown":"The MA trip unit provides short-circuit (magnetic) protection only; there is no thermal overload element, so upstream or separate overload relay handles that function. Rated Icu at 380/415 V AC is 70 kA, dropping to 65 kA at 440 V, 50 kA at 500 V, and 35 kA at 525 V. At 660/690 V AC it still holds 10 kA. Under UL 60947-4-1, Icu is 85 kA at 240 V AC and 65 kA at 480 V AC. Front connections top and bottom. Connection pitch is 35 mm. IP40 protection, IK07 impact resistance. Ambient conditions: 0 to 95 % relative humidity, operating altitude up to 2000 m without derating, 2000–5000 m with derating.","metaTitle":"Schneider C10H3MA050 ComPacT NSX 3P 50A Magnetic Circuit Bre","metaDescription":"Schneider Electric C10H3MA050 ComPacT NSX circuit breaker, 3-pole, 50 A magnetic trip unit (MA), 70 kA at 415 V AC. Motor protection, EN/IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$340.07 – $552.58","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/45cd1ca167b7b46f8cfe670343713eab.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10H3MA050/circuit-breaker-compact-nsx100h-70ka-415vac-3-poles-ma-trip-unit-50a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10H3MA050/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10H3MA050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10H3MA050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}