{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10H3MA100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10H3MA100","canonicalUrl":"https://aoctrl.com/schneider/C10H3MA100","factsUrl":"https://aoctrl.com/api/mcp/products/C10H3MA100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C10H3MA100, 3P 100A MCCB with magnetic trip unit, 70 kA Icu at 415 V AC, motor protection application.","salesMarkdown":"It is a 3-pole unit rated 100 A at 65 °C, with a breaking capacity of 70 kA Icu at 380/415 V AC per IEC 60947-2. The magnetic trip responds to short-circuit faults only — no thermal overload element — so motor overload protection must be handled separately by a thermal relay or motor protection relay upstream. This H-frame breaker delivers 70 kA Icu at 415 V AC, 65 kA at 440 V, and 50 kA at 500 V. At 690 V AC it still holds 10 kA Icu. The high interrupting rating at typical 400 V industrial supply means it can be used as a main or feeder breaker in high-fault panels without cascading upstream. The magnetic trip unit (MA) provides instantaneous short-circuit protection only, with no adjustable time delay — coordination with downstream devices relies on the let-through energy (I²t) of the breaker itself. Front connections for both line and load sides. IP40 enclosure protection and IK07 impact resistance suit panel-mounted installations in industrial environments. Mechanical endurance is 50,000 cycles. Electrical durability varies with load: 50,000 cycles at 440 V at half rated current, 30,000 cycles at full rated current, and 10,000 cycles at 690 V at full rated current.","metaTitle":"C10H3MA100 ComPacT NSX 100A MCCB, 70kA 415V AC Motor Protect","metaDescription":"C10H3MA100 ComPacT NSX 100A MCCB with magnetic trip unit. 70 kA Icu at 415 V AC, motor protection, EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$340.07 – $558.95","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9eab4ed8e7abe9fb650083c76a760117.pdf","sourceUrl":"https://www.se.com/za/en/product/C10H3MA100/circuit-breaker-compact-nsx100h-70ka-at-415vac-ma-trip-unit-100a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10H3MA100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10H3MA100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10H3MA100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}