{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10H44V040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10H44V040","canonicalUrl":"https://aoctrl.com/schneider/C10H44V040","factsUrl":"https://aoctrl.com/api/mcp/products/C10H44V040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX100H, 40 A, 4-pole MCCB with MicroLogic 4.2 electronic trip unit, 100 kA Icu at 240 V AC, integrated earth-leakage protection.","salesMarkdown":"The C10H44V040 is a Schneider Electric ComPacT NSX100H 4-pole MCCB rated 40 A at 40 °C, built around the MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection. At 415 V AC the breaking capacity is 70 kA Icu; at 440 V AC it's 65 kA Icu, so the part holds its interrupting rating well into the 400 V class, not just at low voltage. ## Trip unit and protection logic The MicroLogic 4.2 is an electronic trip unit offering L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection — all in one package. Earth-leakage is integrated, not a bolt-on accessory, which simplifies panel wiring and reduces the component count per feeder. Dimensions: 161 mm H × 140 mm W × 86 mm D. IP40 front face, IK07 impact rating.","metaTitle":"C10H44V040 ComPacT NSX100H 40A 4P MCCB, 100kA Icu at 240V","metaDescription":"C10H44V040 ComPacT NSX100H 40A 4P MCCB with MicroLogic 4.2 electronic trip unit. 100 kA Icu at 240 V AC, integrated earth-leakage protection. Current lifecycle stage. Sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,172.06 – $2,246.40","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b597451839187e66c0fc4fcc2a5a909.pdf","sourceUrl":"https://www.se.com/th/en/product/C10H44V040/circuit-breaker-compact-nsx100h-70ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10H44V040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10H44V040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10H44V040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}