{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10M2TM025","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10M2TM025","canonicalUrl":"https://aoctrl.com/schneider/C10M2TM025","factsUrl":"https://aoctrl.com/api/mcp/products/C10M2TM025","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, 25 A, 2P, thermal-magnetic TM-D trip unit, 85 kA Icu at 220/240 V AC, fixed mount, IP40.","salesMarkdown":"The C10M2TM025 is a Schneider Electric ComPacT NSX100M moulded-case circuit breaker, 2-pole, with a fixed thermal-magnetic TM-D trip unit rated 25 A at 40 °C. At 415 V AC the breaking capacity is still 25 kA Icu, which covers most European distribution boards. Mounts fixed to a backplate — no DIN-rail adapter here. The 70 mm width and 161 mm height fit the standard ComPacT NSX cutout; depth is 86 mm, which leaves room for front-facing cable connections on both line and load sides. IP40 enclosure protection means it is fine inside a cabinet but not for washdown environments. No end-of-life notice or successor has been issued. No second-source or cross-reference exists within the ComPacT family that matches the exact 25 A TM-D 2P configuration without a trip-unit swap. ## What the trip unit does The thermal element responds to sustained overcurrents; the magnetic element trips instantaneously on high fault currents. No earth-leakage protection is built in — that requires a separate Vigi add-on or an external RCD. Power dissipation is 4.01 W per pole, so for a 2-pole breaker expect about 8 W of heat inside the enclosure at rated load.","metaTitle":"Schneider Electric C10M2TM025 ComPacT NSX Circuit Breaker, 2","metaDescription":"Schneider Electric C10M2TM025 ComPacT NSX circuit breaker, 25 A, 2-pole, 85 kA Icu at 220/240 V AC, thermal-magnetic TM-D trip unit. EN/IEC 60947-2. Sourced to order. Request a quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10M2TM025","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"70 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX100M AC/DC, 25kA/415VAC, 2 poles, TMD trip unit 25A","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"25 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 18 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 85 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2","Device short name":"NSX100M","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"25 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"M 25 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.01 W","Protected poles description":"2D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 500 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 85 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"300 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$118.70 – $163.29","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3eb72de38b1a44ca497a63acd1dc8f2d.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10M2TM025/circuit-breaker-compact-nsx100m-ac-dc-25ka-415vac-2-poles-tmd-trip-unit-25a/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C10M2TM025?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability."},{"question":"What is the closest alternative to C10M2TM025 in the ComPacT family?","answer":"No exact pin-compatible alternative exists within the ComPacT NSX family that matches the 25 A, 2-pole, TM-D trip unit without a trip-unit change. A different trip unit rating or pole configuration would require a different order code."},{"question":"What compliance documentation does this brand provide for C10M2TM025?","answer":"The breaker is certified to EN/IEC 60947-2 and carries an overvoltage category III rating. The manufacturer provides a declaration of conformity and a test certificate upon request through the RFQ process."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10M2TM025","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10M2TM025 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}