{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10N1TM100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10N1TM100","canonicalUrl":"https://aoctrl.com/schneider/C10N1TM100","factsUrl":"https://aoctrl.com/api/mcp/products/C10N1TM100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100N, 1-pole, 100 A, TM-D thermal-magnetic trip unit, 25 kA Icu at 240 V AC, toggle control, fixed mount.","salesMarkdown":"The C10N1TM100 is a fixed-mount ComPacT NSX100N 1-pole circuit breaker with a TM-D thermal-magnetic trip unit rated 100 A at 40 °C. It ships as a single unit — toggle handle, front-front connections, no earth-leakage module. The kit is complete for a distribution panel line-up: one breaker, one pole protected, ready for backplate mounting in horizontal or vertical orientation. ## Breaking capacity and what it means for your panel Rated 25 kA Icu at 220/240 V AC 50/60 Hz and 50 kA Icu at 250 V DC per IEC 60947-2. For DC circuits, the 50 kA rating at 250 V DC covers battery banks or rectifier outputs in the same footprint. ## Integration checklist Mounts on a backplate (DIN-rail adapter not included in this fixed-mount variant). Accepts horizontal or vertical orientation flat on the back. Front-front connections simplify bus-bar and cable routing in a panel. Overvoltage category IV covers the main distribution board entry. IP40 enclosure (IK07 impact) keeps dust and tools out; no washdown rating, so keep it inside the cabinet. TM-D trip unit provides L (thermal overload) and I (magnetic short-circuit) protection in one package. The thermal element tracks I²t heating for overloads; the magnetic element trips instantaneously on high fault currents. Utilisation category A means it is not intended for frequent switching of motor starts — this is a distribution breaker, not a motor-circuit protector. ## Durability and thermal budget Mechanical endurance rated 20,000 cycles; electrical endurance 20,000 cycles at 277 V In/2 and 10,000 cycles at 277 V In. Power dissipation per pole is 8.8 W — factor this into enclosure thermal calculations when grouping multiple breakers. Ambient humidity range 0–95 %.","metaTitle":"C10N1TM100 ComPacT NSX100N 1P 100A TM-D Circuit Breaker","metaDescription":"Schneider Electric C10N1TM100 ComPacT NSX100N 1-pole 100 A thermal-magnetic circuit breaker. 25 kA Icu at 240 V AC, EN/IEC 60947-2. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"35 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 250 V DC conforming to IEC 60947-2","Device short name":"NSX100N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"N 25 kA 240 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"8.8 W","Protected poles description":"1D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"277 V AC 50/60 Hz 250 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"25 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 250 V DC conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"800 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$83.49 – $144.13","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bdccf13c3339be5721d0f4959feb7a18.pdf","sourceUrl":"https://www.se.com/vn/en/product/C10N1TM100/circuit-breaker-compact-nsx100n-ac-dc-25ka-240vac-1-pole-tmd-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10N1TM100/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C10N1TM100 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an RFQ for a firm lead time."},{"question":"What is the closest alternative to C10N1TM100 in the ComPacT family?","answer":"Within the ComPacT NSX range, the closest alternative would be a different breaking-capacity variant (e.g., NSX100S or NSX100H) or a different trip-unit rating. The C10N1TM100 is the 1-pole 100 A TM-D with N breaking capacity (25 kA at 240 V AC). Any substitute must match the 1P pole configuration, 100 A frame, and TM-D trip technology to drop in without re-coordination."},{"question":"What compliance documentation does Schneider provide for C10N1TM100?","answer":"The breaker is certified to EN/IEC 60947-2 and suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1 and overvoltage category IV are documented. The manufacturer typically provides a Declaration of Conformity covering the applicable EU directives; specific RoHS/REACH declarations are available from Schneider's product documentation portal."},{"question":"What are the key dimensions of C10N1TM100?","answer":"Height 161 mm, width 35 mm, depth 86 mm. Connection pitch is 35 mm, matching standard bus-bar spacing for 1-pole breakers."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10N1TM100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10N1TM100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}