{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10N32D040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10N32D040","canonicalUrl":"https://aoctrl.com/schneider/C10N32D040","factsUrl":"https://aoctrl.com/api/mcp/products/C10N32D040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, C10N32D040, 3P circuit breaker, 40 A at 40 °C, MicroLogic 2.2 electronic trip unit, 50 kA Icu at 415 V AC, 105 mm width.","salesMarkdown":"The C10N32D040 is a Schneider Electric ComPacT NSX100N frame circuit breaker with a MicroLogic 2.2 electronic trip unit, rated 40 A at 40 °C, 3-pole, and a breaking capacity code of N — 50 kA Icu at 415 V AC. ## Mounting and integration into a distribution panel Mounts on a backplate — not DIN rail — in either horizontal or vertical orientation, flat on the back. The 105 mm width, 161 mm height, and 86 mm depth fit the standard ComPacT NSX cutout; connection pitch is 35 mm. Both line and load connections are front-facing, so busbar or cable routing stays accessible inside the enclosure. ## Electrical durability and thermal memory — what they mean for a motor or distribution load Rated for 50,000 mechanical cycles and 30,000 electrical cycles at 440 V at full rated current (In). That's enough for a main breaker that sees a few operations per day over a 20-year panel life. The trip unit is electronic, not thermal-bimetal, so it holds calibration over temperature and is less prone to drift than a thermal-magnetic breaker. Pollution degree 3 (IEC 60664-1) means it's rated for conductive pollution environments typical of industrial panels. Overvoltage category III suits fixed-installation distribution boards. Compliance documentation (declaration of conformity, CE marking) is available from the manufacturer's documentation portal.","metaTitle":"C10N32D040 ComPacT NSX100N 40A 3P Circuit Breaker, 50kA 415V","metaDescription":"C10N32D040 ComPacT NSX100N circuit breaker, 40 A at 40 °C, 3P, MicroLogic 2.2 electronic trip unit, 50 kA Icu at 415 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10N32D040","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX100N, 50kA at 415VAC, MicroLogic 2.2 trip unit 40A, 3 poles 3d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"40 A at 40 °C","Breaking capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"40 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"N 50 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"1.3 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"18...40 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"600 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$283.91 – $816.32","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b49c76e11363e5f8ec248871225e8e1.pdf","sourceUrl":"https://www.se.com/ae/en/product/C10N32D040/circuit-breaker-compact-nsx100n-50ka-at-415vac-micrologic-2-2-trip-unit-40a-3-poles-3d/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C10N32D040?","answer":"Submit an RFQ against this order code. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is the closest alternative to C10N32D040 in the ComPacT NSX family?","answer":"The ComPacT NSX family includes other frame sizes (NSX160, NSX250) and trip unit ratings. For a direct 40 A, 3-pole, MicroLogic 2.2 electronic trip unit, the C10N32D040 is the specific order code. A higher-current variant would use a different frame and trip unit; there is no pin-compatible drop-in alternative within the same frame."},{"question":"What compliance documentation does Schneider provide for C10N32D040?","answer":"The breaker is CE marked and carries a declaration of conformity to EN/IEC 60947-2. RoHS and REACH compliance documentation is available from Schneider Electric's product documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10N32D040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10N32D040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}