{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10N34V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10N34V100","canonicalUrl":"https://aoctrl.com/schneider/C10N34V100","factsUrl":"https://aoctrl.com/api/mcp/products/C10N34V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C10N34V100, earth leakage circuit breaker, 100 A, 3P, MicroLogic 4.2 trip unit, 50 kA Icu at 415 V AC.","salesMarkdown":"The Schneider C10N34V100 is a ComPacT NSX earth leakage circuit breaker, 3-pole, rated 100 A at 40 °C with a MicroLogic 4.2 electronic trip unit. The 90 kA Icu at 240 V AC is the same breaker on a lower-voltage service; the 10 kA at 690 V AC is the ceiling for a 690 V line. What governs the real-world fit is the 100 A trip unit rating and the integrated earth-leakage protection (the R in the protection type set: L for overload, So for short-time short-circuit with fixed delay, I for instantaneous short-circuit, R for earth-leakage). The electronic trip gives you adjustable long-time pickup and delay, plus the earth-leakage function built in — no add-on module needed. Mounts to a backplate — not a DIN rail. The 105 mm width (3-pole frame) and 161 mm height fit standard ComPacT NSX cutouts; the 86 mm depth leaves room for front-connected cables (upside and downside connections are both front-facing). The IP40 front face keeps dust out; the IK07 impact rating handles accidental tool drops during commissioning. The 35 mm connection pitch is the standard busbar or cable-lug spacing for this frame size. ## What the durability numbers mean for a distribution feeder Mechanical durability is 50,000 cycles — that is the handle life, not the electrical contact life. Electrical durability varies by load: 50,000 cycles at 440 V at half rated current (In/2), 30,000 cycles at 440 V at full rated current (In), 20,000 cycles at 690 V at In/2, and 10,000 cycles at 690 V at In. For a distribution feeder that sees infrequent switching (a few operations a year), these numbers are academic — the breaker will outlast the panel. But if this breaker is used as a disconnect that cycles weekly, the 30,000-cycle figure at 440 V In is the one to watch.","metaTitle":"Schneider C10N34V100 ComPacT NSX 100A Earth Leakage Breaker,","metaDescription":"Schneider C10N34V100 ComPacT NSX earth leakage circuit breaker, 100A, 50kA Icu at 415V. MicroLogic 4.2 trip unit with integrated earth-leakage. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,045.80 – $1,995.84","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/33281030ada76d33fb027e0096e33841.pdf","sourceUrl":"https://www.se.com/za/en/product/C10N34V100/circuit-breaker-compact-nsx100n-50ka-415vac-3-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10N34V100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10N34V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10N34V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}