{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10N3MA013","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10N3MA013","canonicalUrl":"https://aoctrl.com/schneider/C10N3MA013","factsUrl":"https://aoctrl.com/api/mcp/products/C10N3MA013","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100N, circuit breaker, 3P, 12.5 A, MA magnetic trip unit, 50 kA at 415 V AC.","salesMarkdown":"## Motor protection circuit breaker, magnetic-only trip The Schneider Electric C10N3MA013 is a ComPacT NSX100N circuit breaker with a magnetic-only (MA) trip unit, rated 12.5 A at 65 °C. It is designed specifically for motor protection, providing short-circuit protection via magnetic sensing without thermal overload elements — the motor starter or overload relay handles the thermal curve. The 3-pole device carries a 50 kA breaking capacity at 415 V AC (Icu per IEC 60947-2), which means it can safely interrupt fault currents up to that level in a 400 V motor branch circuit without upstream coordination failure. ## Breaking capacity and application context The N-frame (NSX100N) delivers 90 kA Icu at 240 V AC and 50 kA at 415 V AC, tapering to 10 kA at 690 V AC. For a 400 V motor panel, the 50 kA symmetrical rating covers most industrial service-entrance and distribution scenarios. The MA trip unit responds only to magnetic faults — set the instantaneous pickup per the motor inrush and the upstream coordination study. Mounts on a backplate, accepts front-front connections, and fits in a 105 mm wide footprint. ## Durability and environmental ratings Rated for 50,000 mechanical cycles and 50,000 electrical cycles at 440 V at half rated current (In/2). Electrical durability drops to 10,000 cycles at 690 V at full In. IP40 front protection and IK07 impact resistance handle typical panel environments. Operating altitude to 2000 m without derating; derate above that per the manufacturer's curve. Power dissipation is 0.63 W per pole — negligible for enclosure thermal calculations.","metaTitle":"Schneider Electric C10N3MA013 ComPacT NSX100N, 12.5 A, 50 kA","metaDescription":"Schneider Electric C10N3MA013 ComPacT NSX100N circuit breaker, 12.5 A, 3P, MA magnetic trip, 50 kA at 415 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10N3MA013","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX100N, 50kA at 415VAC, MA trip unit 12.5A, 3 poles 3d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"MA","Number of slots":"5 slot(s)","Protection type":"I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"12.5 A at 65 °C","Breaking capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"12.5 A at 65 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Magnetic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"N 50 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"0.63 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"I","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Instantaneous protection pick-up adjustment type Ii":"Adjustable 9 settings","[Isd] Short-time protection pick-up adjustment range":"6...14 x In","[Ii] instantaneous protection pick-up adjustment range":"6...14 x In"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$321.02 – $503.77","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/39e145050ffcbec58c64f20da9e6918c.pdf","sourceUrl":"https://www.se.com/ae/en/product/C10N3MA013/circuit-breaker-compact-nsx100n-50ka-at-415vac-ma-trip-unit-12-5a-3-poles-3d/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C10N3MA013?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is C10N3MA013's listed range?","answer":"It belongs to the Schneider Electric ComPacT range, specifically the ComPacT NSX series."},{"question":"What compliance documentation does this brand provide for C10N3MA013?","answer":"The device is certified to EN/IEC 60947-2 and UL 60947-4-1 standards. It carries suitability for isolation per EN/IEC 60947-2. Specific RoHS/REACH declarations are available from the manufacturer upon request."},{"question":"What is the closest alternative to C10N3MA013 in this family?","answer":"Within the ComPacT NSX100N frame, the closest alternative would be a unit with a different trip unit rating or a thermal-magnetic (TM) trip unit if motor overload protection is needed in the breaker itself. The MA magnetic-only variant is the correct choice when an external overload relay handles the thermal protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10N3MA013","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10N3MA013 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}