{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10N42D040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10N42D040","canonicalUrl":"https://aoctrl.com/schneider/C10N42D040","factsUrl":"https://aoctrl.com/api/mcp/products/C10N42D040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C10N42D040, 4P 40 A MCCB, MicroLogic 2.2 electronic trip unit, 50 kA at 415 V AC, toggle control.","salesMarkdown":"The Schneider Electric C10N42D040 is a 4-pole ComPacT NSX100N molded-case circuit breaker rated 40 A at 40 °C, fitted with an electronic MicroLogic 2.2 trip unit. The toggle control and backplate mounting suit standard panel layouts. At 40 A continuous and 50 kA Icu at 415 V AC, this breaker handles typical 40 A feeder or motor circuits in a 400 V distribution system without needing an upstream current-limiting fuse. The electronic trip unit (MicroLogic 2.2) provides adjustable long-time pickup and delay, plus fixed short-time and instantaneous settings — useful for coordinating with downstream branch breakers in a selective-coordination study. The 4-pole (4P) configuration with neutral on the left covers three-phase plus neutral systems common in European and Asian panel designs. Backplate mounting with front-connect terminals (both upside and downside). IP40 front face and IK07 impact rating suit enclosed panel installation — not for washdown zones. The 5 accessory slots allow field-installable aux contacts, shunt trips, or under-voltage releases without removing the breaker from the panel.","metaTitle":"Schneider Electric C10N42D040 ComPacT NSX 40A 4P MCCB, 50kA","metaDescription":"Schneider Electric C10N42D040 ComPacT NSX circuit breaker, 40A rated, 4-pole, 50 kA at 415 V AC. Electronic MicroLogic 2.2 trip unit. Active production, available to order. RFQ for","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$369.02 – $1,076.17","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/806eecb6cc228785f8f67dbf726d4ae7.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10N42D040/circuit-breaker-compact-nsx100n-50ka-415vac-4-poles-micrologic-2-2-trip-unit-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10N42D040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10N42D040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10N42D040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}