{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10N44V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10N44V100","canonicalUrl":"https://aoctrl.com/schneider/C10N44V100","factsUrl":"https://aoctrl.com/api/mcp/products/C10N44V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX NSX100N, 4P MCCB, 100 A, 50 kA Icu at 415 V AC, MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C10N44V100 is a ComPacT NSX100N 4-pole moulded-case circuit breaker with a MicroLogic 4.2 electronic trip unit, rated 100 A at 40 °C. The MicroLogic 4.2 provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection — all in one electronic trip unit. The earth-leakage is integrated, so you don't need a separate RCCB or add-on module; it monitors residual current directly through the breaker. ## Mounting and integration into a panel Mounts on a backplate in horizontal or vertical orientation, flat on the back. The 4-pole form factor with neutral on the left takes 140 mm width, 161 mm height, and 86 mm depth — measure your enclosure depth before committing; 86 mm is shallow enough for most 200 mm deep enclosures but check the gland plate clearance if you're running cables front-entry (both upside and downside connections are front). The 35 mm connection pitch matches standard busbar systems. Pollution degree 3 (conforming to IEC 60664-1) means it's rated for conductive pollution environments typical of industrial control panels — not just clean office switchgear. Overvoltage category IV covers the main distribution point. The electrical durability figures (50,000 cycles at 440 V In/2, 30,000 at 440 V In) give you a realistic service life for frequent switching applications like capacitor banks or large motor starters.","metaTitle":"Schneider C10N44V100 ComPacT NSX100N MCCB, 100 A, 50 kA","metaDescription":"Schneider Electric C10N44V100 ComPacT NSX100N 4P MCCB with MicroLogic 4.2 electronic trip unit. 100 A at 40 °C, 50 kA Icu at 415 V AC. Integrated earth-leakage protection. EN/IEC 6","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX100N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical durability":"50000 cycles","Breaking capacity code":"N 50 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"5.8 W N 5.8 W L1 and L3 4.9 W L2","Protected poles description":"4D 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"40...100 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,148.69 – $2,155.14","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7902d28b99f5e2831aecf87c210dab31.pdf","sourceUrl":"https://www.se.com/th/en/product/C10N44V100/circuit-breaker-compact-nsx100n-50ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10N44V100/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C10N44V100 and what is the lead time?","answer":"We source and quote the C10N44V100 to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time; no stock or lead-time figures are published here."},{"question":"What compliance documentation does this breaker carry?","answer":"The C10N44V100 is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries IP40 and IK07 ratings per IEC 60529 and IEC 62262. Pollution degree 3 and overvoltage category IV per IEC 60664-1. The manufacturer provides a declaration of conformity; RoHS and REACH documentation is available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10N44V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10N44V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}