{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10N44V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10N44V100","canonicalUrl":"https://aoctrl.com/schneider/C10N44V100","factsUrl":"https://aoctrl.com/api/mcp/products/C10N44V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX NSX100N, 4P MCCB, 100 A, 50 kA Icu at 415 V AC, MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C10N44V100 is a ComPacT NSX100N 4-pole moulded-case circuit breaker with a MicroLogic 4.2 electronic trip unit, rated 100 A at 40 °C. The MicroLogic 4.2 provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection — all in one electronic trip unit. The earth-leakage is integrated, so you don't need a separate RCCB or add-on module; it monitors residual current directly through the breaker. ## Mounting and integration into a panel Mounts on a backplate in horizontal or vertical orientation, flat on the back. The 4-pole form factor with neutral on the left takes 140 mm width, 161 mm height, and 86 mm depth — measure your enclosure depth before committing; 86 mm is shallow enough for most 200 mm deep enclosures but check the gland plate clearance if you're running cables front-entry (both upside and downside connections are front). The 35 mm connection pitch matches standard busbar systems. Pollution degree 3 (conforming to IEC 60664-1) means it's rated for conductive pollution environments typical of industrial control panels — not just clean office switchgear. Overvoltage category IV covers the main distribution point. The electrical durability figures (50,000 cycles at 440 V In/2, 30,000 at 440 V In) give you a realistic service life for frequent switching applications like capacitor banks or large motor starters.","metaTitle":"Schneider C10N44V100 ComPacT NSX100N MCCB, 100 A, 50 kA","metaDescription":"Schneider Electric C10N44V100 ComPacT NSX100N 4P MCCB with MicroLogic 4.2 electronic trip unit. 100 A at 40 °C, 50 kA Icu at 415 V AC. Integrated earth-leakage protection. EN/IEC 6","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In","Mechanical Life Cycles":"50000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,148.69 – $2,155.14","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7902d28b99f5e2831aecf87c210dab31.pdf","sourceUrl":"https://www.se.com/th/en/product/C10N44V100/circuit-breaker-compact-nsx100n-50ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10N44V100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10N44V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10N44V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}