{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10R32D040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10R32D040","canonicalUrl":"https://aoctrl.com/schneider/C10R32D040","factsUrl":"https://aoctrl.com/api/mcp/products/C10R32D040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100R, circuit breaker, 3P, 40 A, MicroLogic 2.2 electronic trip unit, 200 kA Icu at 415 V AC, toggle control, front connection.","salesMarkdown":"## What the 200 kA breaking capacity means for your panel The C10R32D040 is a Schneider Electric ComPacT NSX100R molded-case circuit breaker, 3-pole, rated 40 A at 40 °C with a MicroLogic 2.2 electronic trip unit. For a distribution panel fed from a large transformer or a high-capacity bus, that rating means you do not need an upstream current-limiting fuse; the breaker itself handles the full available fault current at the board. ## Integration and mounting — backplate, not DIN rail Mounts on a backplate (not a DIN rail) in horizontal or vertical orientation, flat on the back. Front connections top and bottom simplify bus-bar or cable landing in a panel layout. The 105 mm width and 161 mm height fit the standard ComPacT NSX footprint; depth is 86 mm, which matters for enclosure depth clearance when the door-mounted rotary handle is used. IP40 front face (IK07 impact rating) means it is protected against tools and small solids but not washdown — fine for a dry indoor panel, not for a food-processing floor.","metaTitle":"C10R32D040 ComPacT NSX 3P 40A, 200 kA at 415 V AC","metaDescription":"Schneider Electric C10R32D040 ComPacT NSX100R circuit breaker, 3P, 40 A, MicroLogic 2.2 electronic trip, 200 kA Icu at 415 V AC. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10R32D040","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX100R, 200kA/415VAC, 3 poles, MicroLogic 2.2 trip unit 40A","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"40 A at 40 °C","Breaking capacity":"200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100R","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"40 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"R 200 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"1.3 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"18...40 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"600 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,411.83","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b042b289483bbc4695d88d825fdd9eec.pdf","sourceUrl":"https://www.se.com/th/en/product/C10R32D040/circuit-breaker-compact-nsx100r-200ka-415vac-3-poles-micrologic-2-2-trip-unit-40a/"},"ai":{"faq":[{"question":"What is the breaking capacity of C10R32D040 at 415 V?","answer":"200 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The rating holds at 200 kA up to 440 V, then derates to 80 kA at 500 V, 65 kA at 525 V, and 45 kA at 690 V."},{"question":"What trip unit does C10R32D040 use?","answer":"A MicroLogic 2.2 electronic trip unit rated 40 A at 40 °C, providing L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection."},{"question":"How do I get current pricing and availability for C10R32D040?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation at quote time."},{"question":"What standards does C10R32D040 comply with?","answer":"It is certified to EN/IEC 60947-2 and suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1, overvoltage category III, and IP40 / IK07 enclosure protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10R32D040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10R32D040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}