{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10R32M050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10R32M050","canonicalUrl":"https://aoctrl.com/schneider/C10R32M050","factsUrl":"https://aoctrl.com/api/mcp/products/C10R32M050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX circuit breaker, C10R32M050, 3P, 50 A, MicroLogic 2.2 M electronic trip unit, 200 kA Icu at 415 V AC, motor protection.","salesMarkdown":"## Motor-protection circuit breaker with MicroLogic 2.2 M trip unit The Schneider Electric C10R32M050 is a ComPacT NSX circuit breaker designed for motor protection, fitted with a MicroLogic 2.2 M electronic trip unit rated 50 A at 65 °C. The trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, with selectable motor tripping classes 10, 5, and 20. Rated 200 kA Icu at 220/240 V, 380/415 V, and 440 V AC; 80 kA at 500 V; 65 kA at 525 V; 45 kA at 660/690 V AC. The R-code (200 kA at 415 V) places this in the high-interrupting tier of the NSX100 frame — suitable for installations with high available fault current, such as large motor control centers or transformer-fed switchboards. ## Mounting and enclosure fit Dimensions 161 mm H x 105 mm W x 86 mm D. IP40 front face (IK07 impact) suits enclosed panel installation — not for washdown environments. Front connections (both upside and downside) simplify bus-bar or cable routing in a fixed-mount MCC bucket.","metaTitle":"Schneider Electric C10R32M050 ComPacT NSX Circuit Breaker, 5","metaDescription":"Schneider Electric C10R32M050 ComPacT NSX circuit breaker with MicroLogic 2.2 M trip unit, 50 A at 65 °C, 200 kA Icu at 415 V. Motor protection, EN/IEC 60947-2. Active production,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10R32M050","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX100R, 200kA at 415VAC, MicroLogic 2.2 M trip unit 50A, 3 poles 3d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2 M","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"50 A at 65 °C","Breaking capacity":"200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100R","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"50 A at 65 °C","Downside connection":"Front","Motor tripping class":"10 5 20","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"R 200 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Complementary motor protection":"Phase unbalance","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"25...50 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","[Ii] instantaneous protection pick-up adjustment range":"750 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$14.74","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3c92d219173da5448b547531cf1e9c16.pdf","sourceUrl":"https://www.se.com/ng/en/product/C10R32M050/circuit-breaker-compact-nsx100r-200ka-at-415vac-micrologic-2-2-m-trip-unit-50a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of C10R32M050?","answer":"200 kA Icu at 220/240 V, 380/415 V, and 440 V AC; 80 kA at 500 V; 65 kA at 525 V; 45 kA at 660/690 V AC, all per IEC 60947-2."},{"question":"What protection curves does the MicroLogic 2.2 M trip unit offer?","answer":"L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection, with motor tripping classes 10, 5, and 20."},{"question":"Where can I buy C10R32M050?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10R32M050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10R32M050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}