{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10R36M050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10R36M050","canonicalUrl":"https://aoctrl.com/schneider/C10R36M050","factsUrl":"https://aoctrl.com/api/mcp/products/C10R36M050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100R, circuit breaker, 3P, 50 A at 65 °C, 200 kA Icu at 415 V AC, MicroLogic 6.2 E-M electronic trip unit, motor protection.","salesMarkdown":"The Schneider Electric C10R36M050 is a ComPacT NSX circuit breaker from the NSX100R frame, fitted with a MicroLogic 6.2 E-M electronic trip unit and rated for motor protection at 50 A at 65 °C. Above that ambient, derating applies per the manufacturer's curve. The MicroLogic 6.2 E-M provides L (long-time overload), So (short-time short-circuit), I (instantaneous), and G (ground fault) protection, with selectable motor tripping classes 5, 10, 20, and 30. Class 10 is standard for general-purpose motor starting; class 20 or 30 accommodates high-inertia loads like fans or centrifuges that take longer to accelerate. At 690 V AC the rating drops to 45 kA Icu — still substantial for a 690 V motor feeder. The breaker carries a utilisation category A (non-selectively coordinated for short-circuit), so it is suited for standalone motor protection or as part of a cascaded system where the upstream device handles selectivity. The 105 mm width and 161 mm height fit standard ComPacT NSX cutouts; depth is 86 mm. Five accessory slots are available for auxiliary contacts, shunt trips, or communication modules. The LCD display on the MicroLogic 6.2 E-M shows energy metering, demand values, and event logs — useful for commissioning and troubleshooting.","metaTitle":"Schneider Electric C10R36M050 ComPacT NSX 50 A, 200 kA Icu","metaDescription":"Schneider Electric C10R36M050 ComPacT NSX circuit breaker, 50 A at 65 °C, 200 kA Icu at 415 V, MicroLogic 6.2 E-M trip unit, motor protection. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.2 E-M","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"50 A at 65 °C","Breaking capacity":"200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100R","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"50 A at 65 °C","Downside connection":"Front","Type of measurement":"Energy meter","Motor tripping class":"30 10 5 20","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Protection and alarm settings Maximeters/minimeters Instantaneous and demand values Phase sequence Demand current and power Maintenance indicators Time-stamped histories and event tables Power quality Energy metering Thermal image function","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"R 200 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Complementary motor protection":"Underload Stalled rotor Protracted starting time Phase unbalance","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20 720 s at 1.5 x Ir for trip class 30 38 s at 6 x Ir for trip class 30 30 s at 7.2 x Ir for trip class 30","[Uimp] rated impulse withstand voltage":"8 kV","[Ig] ground-fault pick-up adjustment range":"0.6...1 x In for In = 25 A 0.3...1 x In for In = 50 A 0.2...1 x In for In > 50 A Ig enable on/off","Long-time protection delay adjustment type tr":"Adjustable","[tg] Ground-fault time delay adjustment range":"0...0.4 s","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"25...50 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable 5 settings","[Ii] instantaneous protection pick-up adjustment range":"750 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$23.28","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/66a16d4b2f4d895dd34a7fb9b9032a69.pdf","sourceUrl":"https://www.se.com/ie/en/product/C10R36M050/circuit-breaker-compact-nsx100r-200ka-415vac-3-poles-micrologic-6-2em-trip-unit-50a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10R36M050/alternatives.json"},"ai":{"faq":[{"question":"What is C10R36M050 used for?","answer":"It is a motor protection circuit breaker for three-phase AC motor feeders, rated 50 A at 65 °C, with electronic trip unit providing overload, short-circuit, and ground-fault protection."},{"question":"Where can I buy C10R36M050?","answer":"It is sourced and quoted to order through independent distribution against an RFQ; current pricing and availability are confirmed at quote time."},{"question":"What compliance documentation does C10R36M050 carry?","answer":"The breaker is certified to EN/IEC 60947-2, with pollution degree 3 per IEC 60664-1 and IK07 impact resistance per IEC 62262. It operates at altitudes up to 2000 m without derating, and up to 5000 m with derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10R36M050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10R36M050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}