{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10R36M080","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10R36M080","canonicalUrl":"https://aoctrl.com/schneider/C10R36M080","factsUrl":"https://aoctrl.com/api/mcp/products/C10R36M080","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C10R36M080, 3P MCCB with MicroLogic 6.2 E-M electronic trip unit, 80 A rated, 200 kA Icu at 415 V AC, motor protection.","salesMarkdown":"The Schneider Electric C10R36M080 is a ComPacT NSX100R three-pole molded-case circuit breaker with a MicroLogic 6.2 E-M electronic trip unit, rated 80 A at 65 °C. It is designed for motor protection — the E-M trip curve provides long-time (L), short-time (So), instantaneous (I), and ground-fault (G) protection, with selectable motor tripping classes 5, 10, 20, and 30. ## Mounting and integration details The LCD display on the MicroLogic trip unit shows energy metering, protection settings, and event logs; the green flashing LED indicates ready state, red LED signals overtemperature at 95 % Ith. ## Durability and thermal memory Mechanical endurance is 20,000 cycles; electrical durability at rated current (80 A, 440 V) is 10,000 cycles, doubling to 20,000 cycles at half-load. The 20-minute thermal memory before and after tripping means the breaker's thermal model retains heat history for that window — useful for re-closing on a motor that has just tripped on overload, avoiding nuisance trips if the motor has not cooled.","metaTitle":"Schneider Electric C10R36M080 ComPacT NSX MCCB, 80 A, 200 kA","metaDescription":"Schneider Electric C10R36M080 ComPacT NSX circuit breaker. 80 A MicroLogic 6.2 E-M trip unit, 200 kA Icu at 415 V AC. Motor protection, EN/IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$23.28","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7920c65ba3a47dc29fe090139ce42f3b.pdf","sourceUrl":"https://www.se.com/ng/en/product/C10R36M080/circuit-breaker-compact-nsx100r-200ka-at-415vac-micrologic-6-2-em-trip-unit-80a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10R36M080/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10R36M080","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10R36M080 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}