{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10V32D040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10V32D040","canonicalUrl":"https://aoctrl.com/schneider/C10V32D040","factsUrl":"https://aoctrl.com/api/mcp/products/C10V32D040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, C10V32D040, 3P, 40 A at 40 °C, MicroLogic 2.2 electronic trip unit, 85 kA Icu at 500 V AC.","salesMarkdown":"The C10V32D040 is a Schneider Electric ComPacT NSX100HB1 circuit breaker, 3 poles, with a MicroLogic 2.2 electronic trip unit rated 40 A at 40 °C. ## Breaking capacity and duty Rated 85 kA Icu at 500 V AC, 80 kA at 525 V AC, and 75 kA at 660/690 V AC (50/60 Hz) per IEC 60947-2. The 20-minute thermal memory before and after tripping ensures the trip curve accounts for prior heating, preventing nuisance trips on repeated inrush events. ## Physical integration and environment Mounts on a backplate (flat on the back), accepts front-connect wiring top and bottom. Dimensions: 161 mm H x 105 mm W x 86 mm D, with a 35 mm connection pitch. IP40 enclosure protection (IK07 impact) suits it for clean indoor panel environments—not washdown or outdoor installation.","metaTitle":"C10V32D040 ComPacT NSX 3P 40A MCCB, 85kA at 500V AC","metaDescription":"Schneider Electric C10V32D040 ComPacT NSX100HB1 circuit breaker, 40A MicroLogic 2.2 trip unit, 85 kA Icu at 500V AC. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$9.11","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d747ca1dc237caacf985cb5bb239a666.pdf","sourceUrl":"https://www.se.com/vn/en/product/C10V32D040/circuit-breaker-compact-nsx100hb1-75ka-690vac-3-poles-micrologic-2-2-trip-unit-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10V32D040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10V32D040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10V32D040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}