{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10V32D100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10V32D100","canonicalUrl":"https://aoctrl.com/schneider/C10V32D100","factsUrl":"https://aoctrl.com/api/mcp/products/C10V32D100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, C10V32D100, 100 A at 40 °C, 85 kA Icu at 500 V AC, 3 poles, MicroLogic 2.2 trip unit.","salesMarkdown":"The C10V32D100 is a Schneider Electric ComPacT NSX circuit breaker from the NSX100HB1 family, rated 100 A at 40 °C with an electronic MicroLogic 2.2 trip unit. The 3-pole design with front-front connections (upside and downside both front) suits standard backplate mounting in a switchboard or MCC bucket. ## Trip unit and protection logic No earth-leakage protection built in; you add a Vigi module externally if ground-fault detection is required. IP40 front face keeps tools and fingers out; IK07 impact rating handles accidental hammer knocks during installation. Mechanical durability is 20,000 cycles; electrical durability varies with load: 20,000 cycles at 440 V In/2, 10,000 cycles at 440 V In, 10,000 cycles at 690 V In/2, and 5,000 cycles at 690 V In. Overvoltage category III and utilisation category A cover distribution-level switching, not motor starting (that would need a category B or motor-protective breaker).","metaTitle":"Schneider Electric C10V32D100 ComPacT NSX100HB1 Circuit Brea","metaDescription":"Schneider Electric C10V32D100 ComPacT NSX circuit breaker, 100 A at 40 °C, 85 kA Icu at 500 V AC. Active production. Quoted to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10V32D100","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX100HB1, 75kA at 690VAC, MicroLogic 2.2 trip unit 100A, 3 poles 3d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100HB1","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"HB1 75 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$8.36","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aabb32c79bcd7b36838e540d3dc72916.pdf","sourceUrl":"https://www.se.com/ae/en/product/C10V32D100/circuit-breaker-compact-nsx100hb1-75ka-at-690vac-micrologic-2-2-trip-unit-100a-3-poles-3d/"},"ai":{"faq":[{"question":"Where can I buy C10V32D100 and how do I get a price?","answer":"C10V32D100 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is C10V32D100's breaking capacity at 500 V AC?","answer":"The breaking capacity is 85 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2."},{"question":"What trip unit does C10V32D100 use?","answer":"It uses a MicroLogic 2.2 electronic trip unit with L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10V32D100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10V32D100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}