{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10V36M050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10V36M050","canonicalUrl":"https://aoctrl.com/schneider/C10V36M050","factsUrl":"https://aoctrl.com/api/mcp/products/C10V36M050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX circuit breaker, C10V36M050, 3-pole, 50 A rated at 65 °C, MicroLogic 6.2 E-M electronic trip unit, 85 kA Icu at 500 V AC.","salesMarkdown":"The C10V36M050 is a Schneider Electric ComPacT NSX circuit breaker, 3-pole, with a MicroLogic 6.2 E-M electronic trip unit rated at 50 A at 65 °C. It's built for motor protection, not just feeder duty — the E-M trip unit gives you adjustable overload (L), short-time (So), instantaneous (I), and ground-fault (G) protection curves, with motor tripping classes 10, 5, 20, and 30 selectable. The 85 kA Icu at 500 V AC is the interrupting rating that governs fault clearing in a motor branch circuit; at 690 V AC it still holds 75 kA Icu, which covers most industrial motor starters. The part sits in the ComPacT NSX family, so it shares the standard backplate mount, front connections, and the 105 mm wide footprint that fits a typical MCC bucket or panel layout. ## Mounting and integration — backplate, front connections, 105 mm wide The 105 mm width (W) and 161 mm height (H) with 86 mm depth (D) fit standard panel layouts. Overvoltage category III covers fixed-installation distribution boards. ## Standards and approvals — EN/IEC 60947-2, IK07 The IK07 impact rating per IEC 62262 means the enclosure withstands a 2 J impact — enough for a tool drop in a panel. The LCD display on the trip unit shows metering data, protection settings, and event logs, which is useful during commissioning without needing a separate communication gateway.","metaTitle":"C10V36M050 ComPacT NSX 50A, 85kA Icu at 500V AC","metaDescription":"C10V36M050 ComPacT NSX circuit breaker, 50A MicroLogic 6.2 E-M trip unit, 85kA Icu at 500V AC. Motor protection, EN/IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$13.23","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8f994cfa227f06006fb81b1fe357f0ff.pdf","sourceUrl":"https://www.se.com/th/en/product/C10V36M050/circuit-breaker-compact-nsx100hb1-75ka-690vac-3-poles-micrologic-6-2em-trip-unit-50a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10V36M050/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10V36M050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10V36M050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}