{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10V3MA100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10V3MA100","canonicalUrl":"https://aoctrl.com/schneider/C10V3MA100","factsUrl":"https://aoctrl.com/api/mcp/products/C10V3MA100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, 3P, 100 A, MA magnetic trip unit, 85 kA Icu at 500 V AC, motor protection.","salesMarkdown":"The Schneider Electric C10V3MA100 is a ComPacT NSX circuit breaker fitted with an MA magnetic-only trip unit, rated 100 A at 65 °C and designed specifically for motor protection — the MA trip responds to short-circuit current only, leaving thermal overload protection to an external relay or motor starter. That 85 kA Icu at 500 V AC (75 kA at 690 V) means it can safely interrupt a fault up to that level without welding contacts or cascading upstream, which matters when you're coordinating a motor branch circuit in a panel with high available fault current. It's a 3-pole (3P) device, suitable for isolation per EN/IEC 60947-2, with a toggle control and front connections on both the line and load sides — standard for panel-mounting on a backplate. The 105 mm width, 161 mm height, and 86 mm depth fit a standard motor control center bucket or distribution panel. Connection pitch is 35 mm — matches common busbar and cable lug spacing.","metaTitle":"Schneider Electric C10V3MA100 ComPacT NSX Circuit Breaker, 1","metaDescription":"Schneider Electric C10V3MA100 ComPacT NSX circuit breaker with MA magnetic trip unit for motor protection. Rated 100 A at 65 °C, 85 kA Icu at 500 V AC. Current production. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$427.07 – $527.74","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f98e44f65805d65916e34e17537b28b3.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10V3MA100/circuit-breaker-compact-nsx100hb1-75ka-690vac-3-poles-ma-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10V3MA100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10V3MA100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10V3MA100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}